Important information    The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.  No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of Schneider Electric.  All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components.  When devices are used for applications with technical safety requirements, the relevant instructions must be followed.  Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operating results.  Failure to observe this information can result in injury or equipment damage.  © 2011 Schneider Electric. All rights reserved.     

Content    Altivar 61 Plus-LH    Drive Systems                        1          Altivar 61 Plus-LH   Configuration guide for 55...630 kW          Content    Drive Systems Content        Drive Systems........................................................................1     Content..................................................................................1     Drive Systems........................................................................2     Overview ...........................................................................................2     Enclosure design ..............................................................................6     Purchase order .................................................................................9     General specification...........................................................13     Quality .............................................................................................13     Mains conditions.............................................................................16     Protection of the plant ....................................................................18     ATV61EX ●●●●●N4H............................................................21     Description......................................................................................21     Specification ...................................................................................23     Connection......................................................................................41     Options ...........................................................................................45     Wiring and connection ........................................................49     Wiring diagram................................................................................49     Options ................................................................................51     Cubicle options...............................................................................51     Cubicle options (depending on power) ..........................................65     Width of the cubicle........................................................................72      

Overview    Altivar 61 Plus-LH    Drive Systems        2                      Drive SystemsOverview  Type of drive    Pumps and fans (industrial environment)    Complex machines                     Type    Altivar 61    Altivar 71            Power range    0.37...800 kW    0.37...630 kW            Voltage ranges    1 AC 200...240 V (0.37...5.5 kW)    1 AC 200...240 V (0.37...5.5 kW)      3 AC 200...240 V (0.75...90 kW)    3 AC 200...240 V (0.37...75 kW)      3 AC 380...480 V (0.75...630 kW)    3 AC 380...480 V (0.75...500 kW)      3 AC 500...690 V (2.2...800 kW)    3 AC 500...690 V (1.5...630 kW)            Output frequency    0.1...500 Hz for the whole power range 0.1...1000 Hz up to 37 kW    0.1...500 Hz for the whole power range 0.1...1000 Hz up to 37 kW            Control method    V/f characteristic (2 or 5 points),  vector-oriented flux control without feedback, energy saving system    V/f characteristic (2 or 5 points),  vector-oriented flux control with/without encoder, ENA system            Interfaces    Removable operating panel,extensible terminals, programmable card "Drive-Controller", multi-pump card, Profibus DP, CANopen, Ethernet TCP/IP, Fipio, Modbus Plus, INTERBUS, Modbus/Uni-Telway, DeviceNet, LonWorks, METASYS N2, APOGEE FLN, BACnet    Removable operating panel, extensible terminals, programmable card "Drive-Controller", multi-pump card, Profibus DP, CANopen, Ethernet TCP/IP, Fipio, Modbus Plus, INTERBUS, Modbus/Uni-Telway, DeviceNet            Protection degree    Built-in units: IP00 / IP20 Wall-mounting devices: IP31    Built-in units: IP00 / IP20 Wall-mounting devices: IP31            Further reading    All information about project planning and order can be found in the product catalogue "Variable speed drives for asynchronous motors Altivar 61" and on www.schneider-electric.com.    All information about project planning and order can be found in the product catalogue "Variable speed drives for asynchronous motors Altivar 71" and on www.schneider-electric.com.   

Overview    Altivar 61 Plus-LH    Drive Systems                        3     Type of drive    Water-cooled frequency inverter     Energy recovery / sinusoidal mains current                Type    Altivar 61Q / Altivar 71Q    Altivar AFE            Power range    90...800 kW    120...860 kW            Voltage ranges    3 AC 380...480 V    3 AC 380...480 V      3 AC 500...690 V    3 AC 500...690 V            Output frequency    0.1...500 Hz for the whole power range    −            Control method    V/f characteristic (2 or 5 points),  vector-oriented flux control with/without encoder, ENA system    −            Interfaces    Removable operating panel, extensible terminals, programmable card "Drive-Controller", multi-pump card, Profibus DP, CANopen, Ethernet TCP/IP, Fipio, Modbus Plus, INTERBUS, Modbus/Uni-Telway, DeviceNet,...    Removable operating panel, extensible terminals, Modbus, CANopen, other fieldbuses my means of option card "Communication bridge"            Protection degree    Built-in units: IP00 / IP20    Built-in units: IP00 / IP20            Further reading    All information about project planning and order can be found in the product catalogue "Variable speed drives for asynchronous motors Altivar 61 or Altivar 71" and on www.schneider-electric.com.    All information about project planning and order can be found in the product catalogue "Variable speed drives for asynchronous motors Altivar 61 or Altivar 71" and on www.schneider-electric.com.   

Overview    Altivar 61 Plus-LH    Drive Systems        4                   Type of drive    Pumps and fans    All drives with high performance in industry,  machine building and automation                    Type    ATV 61 Plus    ATV 71 Plus            Brief description    Altivar Drive Systems with increased protection degree, alternatively in the standard design, with additionally installed options or as a customized solution    Altivar Drive Systems with increased protection degree, alternatively in the standard design, with additionally installed options or as a customized solution            Power ranges    ATV61ES5 ●●●N4  90…630 kW    ATV71ES5 ●●●N4  90…500 kW      ATV61EX ●●●●●N4  90…1400 kW    ATV71EX ●●●●●N4  90…1300 kW      ATV61EX ●●●●●N  90…1800 kW    ATV71EX ●●●●●N  90…1500 kW      ATV61EX ●●●●●Y  110…2400 kW    ATV71EX ●●●●●Y  110…2000 kW            Voltage ranges    ATV61ES5 ●●●N4  380…415 V    ATV71ES5 ●●●N4  380…415 V      ATV61EX ●●●●●N4  400 (380, 415) V    ATV71EX ●●●●●N4  400 (380, 415) V      ATV61EX ●●●●●N  500 (525) V    ATV71EX ●●●●●N  500 (525) V      ATV61EX ●●●●●Y  690 V    ATV71EX ●●●●●Y  690 V      Other voltages are available on request.    Other voltages are available on request.            Output frequency    0.1 … 500 Hz    0.1 … 500 Hz            Control method    V/f characteristic (2 or 5 points),  vector-oriented flux control without feedback, energy saving system    V/f characteristic (2 or 5 points),  vector-oriented flux control with/without encoder, ENA system            Interfaces    Operating panel in the enclosure door with a transparent cover, control terminals alternatively directly in the inverter or in the enclosure,  control terminals can be extended, fieldbus connection via Modbus or CANopen    Operating panel in the enclosure door with a transparent cover, control terminals alternatively directly in the inverter or in the enclosure,  control terminals can be extended, fieldbus connection via Modbus or CANopen            Protection degree    IP23 design of the enclosure  IP54 design of the enclosure IP54 design of the enclosure with separated air flow    IP23 design of the enclosure  IP54 design of the enclosure IP54 design of the enclosure with separated air flow            Further reading    All information about project planning and order can be found in the product catalogue "Variable speed drives for asynchronous motors Altivar 61" and on www.schneider-electric.com.    All information about project planning and order can be found in the product catalogue "Variable speed drives for asynchronous motors Altivar 71" and on www.schneider-electric.com. 

Overview    Altivar 61 Plus-LH    Drive Systems                        5     Type of drive    Low Harmonic Drive            Type    ATV 61 Plus-LH        Brief description    Altivar Low Harmonic Drive Systems with increased protection degree, alternatively in the standard design, with additionally installed options or as a customized solution        Power ranges    55…630 kW        Voltage ranges    400 (380 … 415) V        Output frequency    0.1 … 500 Hz        Control method    V/f characteristic (2 or 5 points),  vector-oriented flux control without feedback, energy saving system        Interfaces    Operating panel in the enclosure door with a transparent cover, control terminals alternatively directly in the inverter or in the enclosure,  control terminals can be extended, fieldbus connection via Modbus or CANopen        Protection degree    IP23 design of the enclosure  IP54 design of the enclosure        Further reading    All information about project planning and order can be found in this document.   

Enclosure design    Altivar 61 Plus-LH    Drive Systems        6                     Enclosure design  Altivar Low Harmonic Drive Systems    The Altivar 61 Plus Low Harmonic Drive is used when drives shouldcontain mains harmonics particularly low.  State-of-the-art components, a new control concept as well as a top-quality filter module reduce the total current distortion factor THD(i) to avalue less than 5 %.  During the development of the enclosure system special attention was paid to the "simpleness" of installation and during operation. The result is anenclosure ready to connect which fulfils the high requirements for the totalcurrent distortion factor THD(i). Consequently, the Altivar 61 Plus-LH is a topical response to energy dissipation and mains pollution.  The modular construction makes it possible to adapt the Altivar 61 Plus-LH to the individual requests. This makes the planning easy and ensures aquick installation and commissioning of the drive.      Basic equipment of the Altivar 61 Plus-LH          This range includes an enclosure which is ready to connect and alreadypre-set. The basic equipment contains a frequency inverter, an ActiveInfeed Converter, a Clean Power filter (EMC filter, line contactor and charging circuit), a line filter choke,a main switch, semiconductor fuses andterminals for comfortable connection.  The design is based on the standard enclosure system Spacial SF with theoperating panel built-in into the door.    The control is located on a spacious swing frame. That ensures compact dimensions, nevertheless it is enough space for additional extensions andaccessibility in case of maintenance.        Device features     Enclosure system      The Spacial SF enclosure system with additional internal reinforcementelements and slide bars for easy installation and removal of the inverterdevices and other power components can be added to any existingenclosure systems.       Operation / parameterization       For safe control, clear parameterization and fast diagnosis, the operatingpanel is installed in the enclosure door at an ideal height. A transparentprotective cover and an adjustable locking code prevent the unintendedparameter adjustments.       Displays on the enclosure      Permanently present status displays that show the actual device state atany time.  Up to 5 analog actual values can be parameterized for the display and thusprovide information on the relevant drive data at any time.      Connection      Generous space is provided to connect the power cables. The extensibilityand accessibility of the control terminals is also taken into consideration.      Extensibility      All enclosure units are equipped with a large, swivelling control panel whichpermits subsequent extensions.      

Enclosure design    Altivar 61 Plus-LH    Drive Systems                        7        Enclosure design 400 V  General technical data Mains voltage  400 (380 … 415) V  ±10%, 50/60 Hz ±5 % for TT, TN-C, TN-S or IT networks  Maximum current  120 % for 60 s per 10 minutes (110 % at ATV61EXC ●D55N4H)  Output voltage  0 … 110 % of line voltage  Operating temperature  0 … +40°C, -10°C ... +50°C with cubicle heating and derating possible  Standards  CE, C-Tick, Gost, EMC filter for 2 nd  "industrial environment" C3 integrated  General design  Enclosure system Spacial SF in RAL 7035 Controls in the enclosure door with additional protective cover,  Cable entry from below, enclosure depth 605 mm (642 mm incl. door handle)  Interfaces  Control terminals directly on the inverter or alternatively in the enclosure, control terminals can be extended, fieldbus connection via Modbus or CANopen    ATV61EXC2●●●N4H  ATV61EXC5●●●N4H IP23CV Compact version  Air flow through grid in enclosure door and mounted air guidance hood,  Enclosure height of 2157 mm  IP54CV Compact version  Air flow through filter mats in enclosure door and a top mounted fan,  Enclosure height of 2237 mm  Standard equipment  Frequency inverter ATV61, Active Infeed Converter, Clean Power Filter (EMC filter, line contactor and charging circuit), line reactor, main switch, mains fuses, control transformer 230 V, 24 V DC power supply, motor terminals, control panel and operating panel in the door  Options  Motor choke, circuit breaker, enclosure plinth, terminal extensions, fieldbus, emergency stop button, safe standstill (control category 3 according to EN 954-1 / ISO 13849-1 for "Safe Standstill" (stop category 0 or 1)), enclosure lighting, enclosure heating, and much more      Dimensions in mm  Type  Motor rating  Output current  Width  Depth (with door  handle)  Height  ATV61EXC2 D55N4H  55 kW  116 A  400  605 (642)  2157  D75N4H  75 kW  160 A  600  605 (642)  2157  D90N4H  90 kW  179 A   600  605 (642)  2157  C11N4H  110 kW  215 A   600  605 (642)  2157  C13N4H  132 kW  259 A   800  605 (642)  2157  C16N4H  160 kW  314 A   800  605 (642)  2157  C22N4H  220 kW  427 A   1200  605 (642)  2157  C25N4H  250 kW  481 A   1600  605 (642)  2157  C31N4H  315 kW  616 A   1600  605 (642)  2157  C40N4H  400 kW  759 A   2000  605 (642)  2157  C50N4H  500 kW  941 A   2000  605 (642)  2157  C63N4H  630 kW  1188 A   2400  605 (642)  2157  ATV61EXC5 D55N4H  55 kW  116 A  400  605 (642)  2237  D75N4H  75 kW  160 A  600  605 (642)  2237  D90N4H  90 kW  179 A   600  605 (642)  2237  C11N4H  110 kW  215 A   600  605 (642)  2237  C13N4H  132 kW  259 A   800  605 (642)  2237  C16N4H  160 kW  314 A   800  605 (642)  2237  C22N4H  220 kW  427 A   1200  605 (642)  2237  C25N4H  250 kW  481 A   1600  605 (642)  2237  C31N4H  315 kW  616 A   1600  605 (642)  2237  C40N4H  400 kW  759 A   2000  605 (642)  2237  C50N4H  500 kW  941 A   2000  605 (642)  2237  C63N4H  630 kW  1188 A   2400  605 (642)  2237     

Enclosure design    Altivar 61 Plus-LH    Drive Systems        8                    

Purchase order    Altivar 61 Plus-LH    Drive Systems                        9          Purchase order  The product designation of the Altivar frequency inverters consists of several points of reference (characters and figures). The meaning of each point is illustrated in the following example.    1 2  3  4  5  6  7  8  9   Ref.  point  ATV 61  E  X  C  5  C25  N4  H   Example                                                                                       Meaning                                                                                                                          Point 9    "H" for LH drive design                                                                                                                          Point 8    Indication of the mains voltage  Always "N4"  3 AC 400 V                                                                                                                          Point 7    Indication of power  D55…D90 for 55…90 kW C11…C90 for 110…630 kW                                                                                                                          Points 5...6    Indication of the protection degree  C2...IP23 C5...IP54 with air intake through filter mats                                                                                                                          Point 4     "X" for configurable system                                                                                                                          Point 3    "E" for enclosure design                                                                                                                          Point 2    "61" for product line Altivar 61                                                                                                                          Point 1    "ATV" for product family Altivar 

Purchase order    Altivar 61 Plus-LH    Drive Systems        10                   Order process for standard enclosures "Configured drive systems"  1. Choose the standard enclosure on the basis of the voltage, the power and the protection degree first.  e.g. mains voltage: 400 V; motor power: 315 kW; protection degree IP54 compact      −  1x  ATV61EXC5C31N4H  Standard enclosure in protection degree IP54 compact        2. Now you can select the desired options, which should be installed into the enclosure in the factory, by means of the option lists.      −  1x  VW3 AE 0104  Isolating handle for switch       −  1x  VW3 AE 1601  Enclosure lighting        Some options affect the dimensions of the enclosure. Please observe chapter "Width of the cubicle", page 72 for this purpose.    3. List the enclosure unit including the respective options in the order:      −  1x  ATV61EXC5C31N4H  Standard enclosure in protection degree IP54 compact       −  1x  VW3 AE 0104  Isolating handle for switch       −  1x  VW3 AE 1601  Enclosure lighting        Specify only one standard enclosure including the respective options per order! Otherwise the assignment of the options to be installed is not possible!  Enclosure options cannot be ordered on its own! This is only possible in combination with a standard enclosure!      4. When you want to order the same enclosure configuration several times, you can simply multiply the individual positions.      −  3x  ATV61EXC5C31N4H  Standard enclosure in protection degree IP54 compact       −  3x  VW3 AE 0104  Isolating handle for switch       −  3x  VW3 AE 1601  Enclosure lighting       

Purchase order    Altivar 61 Plus-LH    Drive Systems                        11     Request and order of "Flexible drive systems" enclosures  For all orders which contain "Options on request" or special options, proceed as follows.    1. Choose the standard enclosure on the basis of the voltage, the power and the protection degree first.  e.g. mains voltage: 400 V; motor power: 400 kW; protection degree IP23      −  1x  ATV61EXC2C40N4H  Standard enclosure in protection degree IP23      2. Now you can select the desired options, which should be installed into the enclosure afterwards, by means of the option lists.  Additionally specify your requests.      −  1x  VW3 AE 1601  Enclosure lighting        −  1x  VW3 AE 0608  Motor choke       −  1x  on request  Special colour RAL6018 "yellow green"       Some options affect the dimensions of the enclosure. Please observe chapter "Width of the cubicle", page 72 for this purpose.      3. List the enclosure unit including the respective options for the request. Send this request to Schneider Electric Power Drives.       −  1x  ATV61EXC2C40N4H  Standard enclosure in protection degree IP23    −  1x  VW3 AE 1601  Enclosure lighting        −  1x  VW3 AE 0608  Motor choke       −  1x  on request  Special colour RAL6018 "yellow green"       Specify additionally the requirements for the special design in the request!    4. You will receive a quotation with a quotation number (e.g. VA-1002-09A-AL) including transfer price (net price), delivery time,  terms of delivery and technical descriptions to the individual positions.      5. Please always quote in the order "ATVCBL" as reference. Add the quotation number and the position in the description.      −  1x  ATVCBL  as per quotation number VA-1002-09A-AL (position 1)    NOTICE  It is absolutely necessary to quote the position in addition to the quotation number so that the amount of the order is well-defined! 

Purchase order    Altivar 61 Plus-LH    Drive Systems        12                    

Quality    Altivar 61 Plus-LH    General specification                        13       General specification  Quality  The Altivar 61 Plus Low Harmonic Drive includes an active input bridge and leads an sinusoidal mains current. So it is an alternative to active and passive filters.   State-of-the-art components, a new control concept as well as a top-quality filter module reduce the total current distortion factor THD(i) of the frequency inverter to a value less than 5 % and by this way it fulfills the requirements according to the recommendations in IEEE 519 to reduce the current harmonics in the mains.  Also in case of operation with partial load the Altivar 61 Plus Low Harmonic leads a sinusoidal mains current with a power factor "cos Phi"  ≈ 1.    A new control concept enables operation without damping resistors, whereby reliability is ensured also in case of distorted mains voltages and also the losses are significantly reduced.     Our high degree of quality awareness ranges from the basic requests in the product specification over the development of the cooling system, of the mechanical design, of the electrical circuit diagram and the individual functions up to the production of the device. This quality level is also long-term guaranteed by means of the corresponding quality assurance systems in the individual business processes and is certified every year by independent authorities according to DIN EN ISO 9001.     The range of Altivar Low Harmonic Drive Systems has been developed especially for applications in the area of industrial and commercial buildings (ventilation, air conditioning and pump technology) where the drive should contain particularly low mains harmonics. It is equipped with several motor control methods and numerous integrated functions. Thus it meets the highest demands in industry, machine building and automation.        The modular construction makes it possible to adapt the it to the individual requests. This makes the planning easy and ensures a quick installation and commissioning of the drive. 

Quality    Altivar 61 Plus-LH    General specification        14                       CE Marking  All devices and drives of the electric drive engineering may cause electromagnetic interferences and otherwise they may be influenced by such interferences. Therefore, they are subject to the  EMC directive 2004/108/EEC since 1.1.1996.  The frequency inverters have an operating voltage which is clearly in the range of 50...1000 V AC or 75...1500 V DC. Therefore, they are also subject to the  Low-voltage directive 2006/95/EEC since 1.1.1997.  Because of the EMC filters which are built into the frequency inverters they are in conformity with  EN 61800-3 and EN 61800-5-1.  Frequency inverters are not considered as machines with at least one mechanically moving part. Therefore, they are not subject to the Machine directive 2006/42/EC.    NOTICE  Frequency inverters are a product of the restricted sales according to IEC 61800-3. In a residential environment this product can cause radio frequency interferences whereupon the user can be called on to take suitable measures.    The frequency inverters have a CE marking on the rating plate. However, it is necessary to observe the installation regulations to achieve the corresponding limits.      Installation regulations  ■  The Altivar 61 Plus-LH includes an EMC filter for industrial environments which is built-in as standard. ■  Use of screened (shielded) motor cables, proper connection of the motor cables on both ends or proper laying in a metallic,  closed and interconnected cable conduit  ■  Use of a motor choke in case of high motor cable lengths ■  Use and proper connection of screened (shielded) control cables ■  Grounding of the frequency inverter for human protection ■  Consider the protective separation when preparing control lines and coupling relays ■  Separate laying of the motor cables from other cables, especially from the control wiring 

Quality    Altivar 61 Plus-LH    General specification                        15         Machine safety  The function "Safe Standstill" (page 58) is available as selectable option in various safety and stop categories. So an optimal adaptation of the drive to the required safety category for the machine is possible.   Following variants of the option "Safe Standstill" are selectable:  •  Safety category 1 with stop category 0  with safety input at the inverter   •  Safety category 3 with stop category 0   with Preventa safety relay  •  Safety category 3 with stop category 1  with Preventa safety relay and monitored deceleration of the drive    NOTICE  For all selectable safety options the implementation of external safety-relevant contacts is provided.  So the ATV61 Plus does not act as a closed safety system in terms of the Machine directive and safety standards EN/IEC 61508, EN 954-1, ISO 13849-1 and NF EN 62061. It has to be accounted as component in any case. The safety-relevant components which are installed in the ATV61 Plus and their safety-relevant functionality have to be included in the whole machine safety by the engine builder.      Human protection PELV  The device fulfills the requirements for protective separation between power and electronic connections according to EN 61800-5-1.        DANGER   HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH All connected external equipments must fulfil the requirements for protective separation. Failure to follow this instruction will result in death or serious injury. 

Mains conditions    Altivar 61 Plus-LH    General specification        16                       Mains conditions  Mains voltage  The Altivar 61 Plus-LH devices are designed for the following mains voltages:    3 AC 400 (380 … 415) V  ± 10 %, 50/60 Hz ± 5 %    The nominal mains voltage must be set at the Active Infeed Converter and the inverter by means of a parameter. Thereby an optimal adjustment of the undervoltage protective function takes place.      CAUTION  INCOMPATIBLE LINE VOLTAGE Please ensure that the line voltage corresponds with the supply voltage of the frequency inverter before you switch the inverter on to configure it. An incompatible line voltage may cause damage of the inverter.  Failure to follow this instruction can result in injury or equipment damage.      Nongrounded mains  The use of the Altivar 61 Plus-LH is basically in all network variants permitted.    With the option "Design for IT networks" (page 61) the frequency inverter is prepared for connection to non-grounded networks.  In case of nongrounded mains a single ground (earth) fault in the supplying mains has no effect to the function of the inverter. If the ground (earth) fault occurs in the motor or the motor cables, the inverter is switched off.  But the recognition heavily depends on the ground (earth) capacitance of the mains.        DANGER   HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH Install in IT networks only special EMC filters with very low leakage current (increase of earth capacitance,...)  Failure to follow these instructions will result in death or serious injury.        Radio frequency interferences  The frequency inverters include an EMC filter built-in as standard. This filter complies with the requirements for category "C3  –Industrial environments" according EN/IEC 61800-3 (in the past: EN 55011 class A group 2).      NOTICE  Frequency inverters are a product of the restricted sales according to IEC 61800-3. In a residential environment this product can cause radio frequency interferences whereupon the user can be called on to take suitable measures.   

Mains conditions    Altivar 61 Plus-LH    General specification                        17         Mains impedance / Short-circuit current  The frequency inverters are designed considering a maximal permitted mains short-circuit current of the supply (values see technical data of the respective frequency inverter).  Optionally the devices can be also designed for higher mains short-circuit currents.      Power factor correction systems  Frequency inverters cause current harmonics in the supplying mains. When a power factor correction system is used, their capacitors are additionally stressed by means of the harmonics.  To protect against overload, we recommend the installation of chokes for those parts.      Switching rate  The Altivar 61 Plus-LH includes a line contactor which is activated in case of a start command. A stop command disconnects the power part of the Altivar 61 Plus-LH from the mains.    NOTICE  By means of the certificated control input "PWR" a "Safe Standstill" of the drive is considering the safety category according to EN 954-1 / ISO 13849-1 (and IEC/EN 61800-5-2).    Inverter control  Switching rate  The Altivar 61 Plus-LH is controlled via a start/stop command.  max. 60 switching operations per hour (safety category 1, stop category 0)  Electronic lock of the inverter by means of the control input PWR "Safe Standstill"  arbitrary (safety category 3, stop category 0 or 1)   

Protection of the plant    Altivar 61 Plus-LH    General specification        18                       Protection of the plant    Responsibility  All stated connection recommendations and planning remarks are to be taken merely as suggestions which must be adapted to the local conditions and regulations concerning installation and usage.   This applies especially to the safety regulations for machines, the EMC regulations and the general regulations for human protection.      WARNING  HUMAN PROTECTION AND MACHINE SAFETY Integrate the frequency inverter into the protection and safety concept of the plant or machine.  Failure to follow this instruction can result in death, serious injury and/or equipment damage.      Frequencies  60 Hz      CAUTION  OPERATION AT FREQUENCIES 60 Hz Check whether the used components are qualified for operation at frequencies higher than 60 Hz. Ask the manufacturer of the motor and the machine if necessary.   Failure to follow this instruction can result in injury or equipment damage.      Overvoltage protective circuit  A free-wheeling diode is provided for DC control circuits.  For AC control circuits the R/C wiring is preferable compared to a wiring with varistors because as a result not only the peak overvoltage is reduced but also the rise-time.    CAUTION  RISK OF MALFUNCTIONS IN THE CONTROL CIRCUITS All inductances like relays, contactors, magnetic brakes, etc. have to be equipped with an overvoltage protective circuit. It helps to prevent malfunctions of the conventional device control as well as of the fieldbus.  The protective circuit must be qualified for inverter operation !  Failure to follow this instruction can result in equipment damage. 

Protection of the plant    Altivar 61 Plus-LH    General specification                        19         Residual current circuit breaker  Frequency inverters, especially those with additional EMC filters and screened (shielded) motor cables, lead an increased leakage current against ground (earth).  The leakage current depends on:  •  the length of the motor cable •  the type of laying and whether the motor cable is screened (shielded) or not •  the set pulse frequency •  the use of an additional radio frequency interference filter •  the grounding of the motor at its installation place (grounded or nongrounded)    Depending on the conditions, the leakage current of plants with high cable lengths can be absolutely higher than 100 mA !  The built-in residual current detection has no current-limiting effect. It only helps to protect the drive and is no human protection.    CAUTION  INCORRECT TRIGGERING OF THE RESIDUAL CURRENT CIRCUIT BREAKER Particularly because of the capacitors of the radio frequency interference filter, an unintentional triggering of a ground (earth) leakage circuit breaker may occur at the moment of switching on. As well, the ground (earth) capacitances may cause an incorrect triggering during operation. On the other hand, it is possible that the triggering is blocked by means of DC components which are caused by the mains rectification at the input of the inverter.  Therefrom, you should observe following:  ■  Only use short-time delayed and pulse current sensitive residual current circuit breakers with considerably higher tripping  current.  ■  Protect the other loads by means of a separate residual current circuit breaker. ■  Residual current circuit breakers in front of an inverter do not provide absolutely reliable protection in case of direct contact !!  So they should be always used in combination with other protective measures.  ■  The frequency inverters have no current-limiting effect (in case of residual currents) and therefore they do not violate the  protective multiple grounding.  Failure to follow these instructions can result in equipment damage.      Automatic restarting  In case line fault the Altivar 61 Plus-LH changes to drive state "USA" and shows the alarm message USA [Undervoltage alarm] at the display. When the mains voltage returns within 15 seconds and a start command is given, the drive automatically restarts.  If the mains voltage does not return within 15 seconds, the Altivar 61 Plus-LH changes to drive state "External fault" and signalizes it via the status relay.    When an automatic restart is not permitted for safety reasons, the following functions of the inverter can be adjusted:  ■  Trip state after each mains disconnection or line fault  Menu:  [1.8 FAULT MANAGEMENT] (FLt-)  Parameter:  USb [UNDERVOLTAGE MGT]  Setting  [Std fault] (0)  ■  Selection of the start command 2-wire control edge rated or 3-wire control 

Protection of the plant    Altivar 61 Plus-LH    General specification        20                       Operation without energy return  The Altivar 61 Plus-LH supplies energy back into the mains during generator operation. When this function is not desired (e.g. in case of operation at diesel generators), the following functions must be adapted.    Active Infeed Converter AIC (LCD operating panel in the enclosure):  Menu:  [4.1 Process protection]  Parameter:   4.1.01 [I max 1 generator]  Setting: 10%    Inverter Altivar 61 (LCD operating panel in the enclosure door): Menu:  [1.7 APPLICATION FUNCT.] (FUn-)  Parameter:  brA [Dec. ramp adapt.]  Setting: [Yes]  (YES)      Locking of the frequency inverter  The Altivar 61 Plus-LH devices include the standard protective function "Safe Standstill" (Power Removal), which helps to prevent any unintended start-up of the motor. This function fulfills, when correctly wired, the machine standard EN 954-1 / ISO 13849-1 safety category 3, the IEC/EN 61508 SIL2 standard for functional safety and the power drive system standard IEC/EN 61800-5-2. 

Description    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V                       21       ATV61EX ●●●●●N4H  Line supply voltage 400 V   Description    Altivar 61 Plus-LH in standard enclosures for 400 V mains  The basic equipment contains:       ■  Frequency inverter ATV61 ■ Active Infeed Converter ■ Clean Power Filter with integrated EMC filter ■ Line reactor ■ Mains connection on main switch ■  Main switch (without door handle) ■ Superfast semiconductor fuses for inverter protection ■ Control transformer for 230 V AC ■ 24 V DC power supply ■  LCD operating panel (mounted into the enclosure door) ■ Terminals/bars for motor connection ■ Protection degree IP23:  air inlet through air inlet grill in the enclosure door, air outlet through the enclosure roof.  ■ Protection degree IP54:  air inlet through air inlet grill in the enclosure door, air outlet through filter fans at the enclosure roof.  ■  Max. inflow coolant temperature 0...40°C ■ Enclosure Spacial SF, color RAL 7035 ■ Multilingual operating instructions ■  Documentation-CD-ROM with parameterization instructions, fieldbus  instructions, operating and parameterizing software,...  ■ Enclosure layout plans consisting of circuit diagram, terminal  connection table, list of materials and design drawing     

Description    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V       22                    

Specification    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V                       23         Specification    General technical data  Input    Voltage  400 (380 … 415) V  ±10% for TT, TN-C, TN-S or IT networks  Frequency  50 / 60 Hz  ±5 %  Total current distortion factor THD(i)  ≤5 % (at sinusoidal mains voltage)  Overvoltage class  Class III according to EN 50178  Output    Control method  Vector-oriented flux control without feedback, V/f characteristic, energy saving system  Voltage  3 AC 0...110% line supply voltage, dynamic voltage stabilization  Overload  20 % for 60 seconds per 10 minutes (10 % at ATV61EXC ●D55N4H)  Pulse frequency  2.5 kHz, adjustable from 2...8 kHz  Frequency / Base frequency  0.1...500 Hz / 25...500 Hz, adjustable  Short circuit protection  All-pole protected against short circuit and earth fault by means of overcurrent switch-off  Design Floor-standing  enclosure  Cooling forced Speed accuracy  V/f mode:  slip frequency  VC without feedback  0.3 x slip frequency  Mechanical strength    Mechanical vibration  According to IEC/EN 60068-2-6 1.5 mm at 3...10 Hz, 0.6 g at 10...200 Hz (3M3 according to IEC/EN 60721-3-3)  Shock  According to IEC/EN 60068-2-27 4 g for 11 ms (3M2 according to IEC/EN 60721-3-3)  Ambient conditions    Operating temperature  0...+40°C (-10...+40°C with enclosure heating) 3K3 according to IEC/EN 60721-3-3 up to +50°C with derating  Storage / Transport temperature  -25...+70°C  Protection degree  selective: ATV61EXC2 ●●●N4H ... IP23  ATV61EXC5 ●●●N4H ... IP54 with air intake through filter mats  Environmental class / Humidity  Class 3K3 in accordance with IEC/EN 60721-3-3 / no condensation,  max. 95 % relative humidity  Altitude  Up to 1000 m, beyond power decrease of 1 % per 100 m up to 3000 m  Allowed pollution  Pollution degree: for IP23 design: pollution degree 2 according to EN 61800-5-1 for IP54 design: pollution degree 3 according to EN 61800-5-1  Chemical / mechanical classification: 3C2 and 3S2 according to EN 60721-3-3  Protection class  Class 1 according to EN 50178  Standards    Basic standard  The devices are designed, built and tested on the basis of EN 61800-2, EN 61800-3, EN 61800-5-1 and EN 60204-1.  EMC immunity  According to EN 61800-3, 1 st  and 2 nd  environment   (IEC 1000-4-2; IEC 1000-4-3; IEC 1000-4-4; IEC 1000-4-5; IEC 1000-4-6)  EMC emission  In accordance with product standard EN 61800-3, 2nd environment, category C3  Insulation  Galvanic insulation in accordance with EN 61800-5-1 PELV  (Protective Extra Low Voltage)  Standards  CE, C-Tick, Gost      NOTICE  Frequency inverters are a product of the restricted sales according to IEC 61800-3. In a residential environment this product can cause radio frequency interferences whereupon the user can be called on to take suitable measures.     

Specification    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V       24                   Protection degree ATV61EXC● and ATV61EXS5  In order to adapt the utmost robust Altivar product line with enclosure design optimal to the individual requests of the system, these enclosure units are available in two different designs. Each solution contains a clearly specified and tested cooling system which provides highest operating safety.    The standard design of the Altivar 61 Plus-LH enclosure units complies with protection degree IP23. If a higher protection degree is desired or required, there is an IP54 solution available.    Overview of standardised protection degrees ATV61EXC2 - Standard enclosure design IP23    In this case the input of the cooling air takes place by the enclosure door and the output through the top of the enclosure. The air flow must not be constrained by means of fixtures or filter mats.    3 5 4 1 2     1  Frequency inverter ATV61 and Active Infeed Converter  2  Clean Power Filter components  3  Air inlet grid (without filter mat) for control part and power part  4  Metal cover with splash water protection  5  Guided air flow to avoid internal air short-cuts    Protection degree: IP23  Air inlet temperature: 0...+40°C (-10...+40°C with enclosure heating)                                           

Specification    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V                       25     ATV61EXC5 - Enclosure design IP54    At protection degree IP54 with filter mats the input of the cooling air takes place through the filter mats in the enclosure door and the output through the fan at the top of the enclosure.    3 4 1 2     1  Frequency inverter ATV61 and Active Infeed Converter  2  Clean Power Filter components  3  Air inlet grid (with filter mat)  4  Fan (with filter mat)    Protection degree: IP54  Air inlet temperature: 0...+40°C (-10...+40°C with enclosure heating)   

Specification    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V       26                       Technical data  Type  ATV61EX●●    D55N4H  Built-in standard device  ATV61HD55N4  Nominal data Motor rating P N  [kW]   V N  = 400 V  55  Continuous output current I N  [A]   V N  = 400 V  116  Maximum current for 60 s per 10 minutes I MAX  [A]   V N  = 400 V  128  Input Input current I IN  [A]   V N  = 400 V  93  I Harm  [A] )  V N  = 400 V  4.4  Continuous apparent power S N  [kVA]   V N  = 400 V  64  Characteristics Efficiency [%]  ≥ 94.0  Losses [W]  at I N  3370  Weight net/gross [kg] ATV61EXC2 ●●●N4H  325 / 370  ATV61EXC5 ●●●N4H  325 / 370  Ambient conditions Air flow [m 3 /h] 880  Sound pressure level [dB(A)]   EXC2 / EXC5  77 / 76  Mains short circuit current [kA]  5.5 / 100 )    ) … Value only valid at sinusoidal mains voltage.  ) … Value only valid with option circuit breaker or in combination with pre-fuses, see chapter “Fuses and cable cross sections".  Dimensions: IP23CV Compact version    ATV61EXC2D55N4H       Altivar Plus L1 L2 L3 F1 F2 F3 U VW 400 2002 155 605 642  

Specification    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V                       27     Dimensions: IP54CV Compact version    ATV61EXC5D55N4H        Altivar Plus L1 L2 L3 F1 F2 F3 U VW 400 2002 235 605 642   NOTICE  The total dimensions of the enclosure including options are given in chapter "Width of the cubicle", page 72.    NOTICE   Due to the compact dimensions of the ATV61EX ●●D55N4H the general enclosure options, page page 45 are only available on  request      

Specification    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V       28                     Type  ATV61EX●●    D75N4H  D90N4H  C11N4H  Built-in standard device  ATV61HD75N4  ATV61HD90N4  ATV61HC11N4  Nominal data Motor rating P N  [kW]   V N  = 400 V  75  90  110  Continuous output current I N  [A]   V N  = 400 V  160  179  215  Maximum current for 60 s per 10 minutes I MAX  [A]   V N  = 400 V  192  215  258  Input Input current I IN  [A]   V N  = 400 V  126  150  177  I Harm  [A] )  V N  = 400 V  6.0  7.1  8.4  Continuous apparent power S N  [kVA]   V N  = 400 V  87  104  123  Characteristics Efficiency [%]  ≥ 94.0  ≥ 94.6  ≥ 94.6  Losses [W]  at I N  4820  4890  6270  Weight net/gross [kg] ATV61EXC2 ●●●N4H  420 / 465  420 / 465  435 / 480  ATV61EXC5 ●●●N4H  420 / 465  420 / 465  435 / 480  Ambient conditions Air flow [m 3 /h] 880  880  880  Sound pressure level [dB(A)]   EXC2 / EXC5  77 / 76  77 / 76  77 / 76  Mains short circuit current [kA]  8.5 / 100 )  8.5 / 100 )  8.5 / 100 )    ) …  Value only valid at sinusoidal mains voltage.  ) …  Value only valid with option circuit breaker or in combination with pre-fuses, see chapter “Fuses and cable cross sections".  Dimensions: IP23CV Compact version    ATV61EXC2D75N4H … C11N4H       Altivar Plus L1 L2 L3 U V W F1 F2 F3 600 2002 155 605 642    

Specification    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V                       29     Dimensions: IP54CV Compact version    ATV61EXC5D75N4H … C11N4H        Altivar Plus L1 L2 L3 U V W F1 F2 F3 600 2002 235 605 642   NOTICE  The total dimensions of the enclosure including options are given in chapter "Width of the cubicle", page 72. 

Specification    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V       30                     Type  ATV61EX●●    C13N4H  C16N4H  Built-in standard device  ATV61HC13N4  ATV61HC16N4  Nominal data Motor rating P N  [kW]   V N  = 400 V  132  160  Continuous output current I N  [A]   V N  = 400 V  259  314  Maximum current for 60 s per 10 minutes I MAX  [A]   V N  = 400 V  311  377  Input Input current I IN  [A]   V N  = 400 V  212  255  I Harm  [A] )  V N  = 400 V  10.1  12.1  Continuous apparent power S N  [kVA]   V N  = 400 V  147  177  Characteristics Efficiency [%]  ≥ 95.3  ≥ 95.3  Losses [W]  at I N  6450  7540  Weight net/gross [kg] ATV61EXC2 ●●●N4H  555 / 605  560 / 610  ATV61EXC5 ●●●N4H  550 / 600  555 / 605  Ambient conditions Air flow [m 3 /h] 1200  1200  Sound pressure level [dB(A)]   EXC2 / EXC5  69 / 76  69 / 76  Mains short circuit current [kA]  8.5 / 100 )  20 / 100 )    ) … Value only valid at sinusoidal mains voltage.  ) … Value only valid with option circuit breaker or in combination with pre-fuses, see chapter “Fuses and cable cross sections".  Dimensions: IP23CV Compact version    ATV61EXC2C13N4H, C16N4H        Altivar Plus 800 Netz/Mains L1 L2 L3 Motor U V W -F 101 -F 102 -F 103 2002 155 605 642  

Specification    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V                       31     Dimensions: IP54CV Compact version    ATV61EXC5C13N4H, C16N4H        Altivar Plus 800 Netz/Mains L1 L2 L3 Motor U V W -F 101 -F 102 -F 103 2002 235 605 642     NOTICE  The total dimensions of the enclosure including options are given in chapter "Width of the cubicle", page 72. 

Specification    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V       32                     Type  ATV61EX●●    C22N4H  Built-in standard device  ATV61HC22N4  Nominal data Motor rating P N  [kW]   V N  = 400 V  220  Continuous output current I N  [A]   V N  = 400 V  427  Maximum current for 60 s per 10 minutes I MAX  [A]   V N  = 400 V  512  Input Input current I IN  [A]   V N  = 400 V  348  I Harm  [A] )  V N  = 400 V  16.6  Continuous apparent power S N  [kVA]   V N  = 400 V  241  Characteristics Efficiency [%]  ≥ 95.5  Losses [W]  at I N  8770  Weight net/gross [kg] ATV61EXC2 ●●●N4H  755 / 820  ATV61EXC5 ●●●N4H  745 / 810  Ambient conditions Air flow [m 3 /h] 1600  Sound pressure level [dB(A)]   EXC2 / EXC5  70 / 77  Mains short circuit current [kA]  20 / 100 )    ) … Value only valid at sinusoidal mains voltage.  ) … Value only valid with option circuit breaker or in combination with pre-fuses, see chapter “Fuses and cable cross sections".  Dimensions: IP23CV Compact version    ATV61EXC2C22N4H      Altivar Plus 600 600 1200 U V W L1 L2 L3 2002 155 605 642    

Specification    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V                       33     Dimensions: IP54CV Compact version    ATV61EXC5C22N4H        Altivar Plus 600 600 1200 U V W L1 L2 L3 2002 235 605 642       NOTICE  The total dimensions of the enclosure including options are given in chapter "Width of the cubicle", page 72. 

Specification    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V       34                     Type  ATV61EX●●    C25N4H  C31N4H  Built-in standard device  ATV61HC25N4  ATV61HC31N4  Nominal data Motor rating P N  [kW]   V N  = 400 V  250  315  Continuous output current I N  [A]   V N  = 400 V  481  616  Maximum current for 60 s per 10 minutes I MAX  [A]   V N  = 400 V  577  739  Input Input current I IN  [A]   V N  = 400 V  395  495  I Harm  [A] )  V N  = 400 V  18.8  23.6  Continuous apparent power S N  [kVA]   V N  = 400 V  274  343  Characteristics Efficiency [%]  ≥ 95.5  ≥ 95.5  Losses [W]  at I N  11670  14520  Weight net/gross [kg] ATV61EXC2 ●●●N4H  900 / 980  900 / 980  ATV61EXC5 ●●●N4H  915 / 995  915 / 995  Ambient conditions Air flow [m 3 /h] 2400  2400  Sound pressure level [dB(A)]   EXC2 / EXC5  70 / 78  70 / 78  Mains short circuit current [kA]  20 / 100 )  20 / 100 )    ) … Value only valid at sinusoidal mains voltage.  ) … Value only valid with option circuit breaker or in combination with pre-fuses, see chapter “Fuses and cable cross sections".  Dimensions: IP23CV Compact version    ATV61EXC2C25N4H, C31N4H      800 Altivar Plus 800 1600 U U V V W W L1 L2 L3 2002 155 605 642    

Specification    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V                       35     Dimensions: IP54CV Compact version    ATV61EXC5C25N4H, C31N4H      800 Altivar Plus 800 1600 U U V V W W L1 L2 L3 2002 235 605 642     NOTICE  The total dimensions of the enclosure including options are given in chapter "Width of the cubicle", page 72. 

Specification    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V       36                     Type  ATV61EX●●    C40N4H  C50N4H  Built-in standard device  ATV61HC40N4  ATV61HC50N4  Nominal data Motor rating P N  [kW]   V N  = 400 V  400  500  Continuous output current I N  [A]   V N  = 400 V  759  941  Maximum current for 60 s per 10 minutes I MAX  [A]   V N  = 400 V  911  1129  Input Input current I IN  [A]   V N  = 400 V  628  780  I Harm  [A] )  V N  = 400 V  29.9  37.1  Continuous apparent power S N  [kVA]   V N  = 400 V  435  540  Characteristics Efficiency [%]  ≥ 95.8  ≥ 95.8  Losses [W]  at I N  17030  21730  Weight net/gross [kg] ATV61EXC2 ●●●N4H  1360 / 1455  1360 / 1455  ATV61EXC5 ●●●N4H  1375 / 1470  1385 / 1480  Ambient conditions Air flow [m 3 /h] 3600  3600  Sound pressure level [dB(A)]   EXC2 / EXC5  71 / 79  71 / 79  Mains short circuit current [kA]  35 / 100 )  35 / 100 )    ) … Value only valid at sinusoidal mains voltage.  ) … Value only valid with option circuit breaker or in combination with pre-fuses, see chapter “Fuses and cable cross sections".  Dimensions: IP23CV Compact version    ATV61EXC2C40N4H, C50N4H      2002 155 605 642 Altivar Plus 1000 1000 2000 U V W L1 L2 L3    

Specification    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V                       37     Dimensions: IP54CV Compact version    ATV61EXC5C40N4H, C50N4H      Altivar Plus 1000 1000 2000 U V W L1 L2 L3 2002 235 605 642     NOTICE  The total dimensions of the enclosure including options are given in chapter "Width of the cubicle", page 72. 

Specification    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V       38                     Type  ATV61EX●●    C63N4H  Built-in standard device  ATV61HC63N4  Nominal data Motor rating P N  [kW]   V N  = 400 V  630  Continuous output current I N  [A]   V N  = 400 V  1188  Maximum current for 60 s per 10 minutes I MAX  [A]   V N  = 400 V  1426  Input Input current I IN  [A]   V N  = 400 V  980  I Harm  [A] )  V N  = 400 V  46.7  Continuous apparent power S N  [kVA]   V N  = 400 V  679  Characteristics Efficiency [%]  ≥ 95.8  Losses [W]  at I N  27460  Weight net/gross [kg] ATV61EXC2 ●●●N4H  1650 / 1755  ATV61EXC5 ●●●N4H  1665 / 1770  Ambient conditions Air flow [m 3 /h] 4800  Sound pressure level [dB(A)]   EXC2 / EXC5  72 / 79  Mains short circuit current [kA]  35 / 100 )    ) … Value only valid at sinusoidal mains voltage.  ) … Value only valid with option circuit breaker or in combination with pre-fuses, see chapter “Fuses and cable cross sections".  Dimensions: IP23CV Compact version    ATV61EXC2C63N4H      1200 Altivar Plus 1200 2400 -C 03 /-R03 -C 04 /-R04 -C 05 /-R05 -K01 -K03 L1 L2 L3 U V W 2002 155 605 642      

Specification    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V                       39     Dimensions: IP54CV Compact version    ATV61EXC5C63N4H      1200 Altivar Plus 1200 2400 -C03 /-R03 -C04 /-R04 -C05 /-R05 -K01 -K03 L1 L2 L3 U V W 2002 235 605 642       NOTICE  The total dimensions of the enclosure including options are given in chapter "Width of the cubicle", page 72. 

Specification    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V       40                       Power decrease  Depending on the chosen pulse frequency and the maximum ambient temperature a power increase is possible or a power reduction is necessary. This can be determined by means of the following diagrams.   ATV 61EX●●D55N4H … EX●●C63N4H             Please observe the following guidelines to guarantee trouble-free operation of the drive:  •  At higher pulse frequencies the allowed motor cable length is reduced (see chapter "Motor cable lengths").  •  Select a motor that is at most one type bigger.      NOTICE  If the heat sink temperature is too high, the pulse frequency is automatically reduced to prevent an overload of the inverter. 

Connection    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V                       41         Connection    Fuses and cable cross sections  The Altivar enclosure designs have input fuses built-in as standard. These fuses are for the case that the electronic protective mechanism of the inverter fails. So they are a secondary protection of the inverter.    The below-mentioned diameters for 3-wire cables are recommended values for laying the cable in air at max. 40°C ambient temperature, based on the regulations ÖVN EN 1 and VDE 0100.    The motor cables are dimensioned for the maximum continuous current. They apply to 0...100 Hz (up to 300 Hz the cable losses increase about 25 % because of the Skin-effect).        DANGER   HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH ■  I case of other ambient conditions and different regulations the cable diameters must be adjusted. ■  The dimensioning of the pre-fuses, mains cable cross sections and mains cable length has to be done in observance to the  available mains short circuit current to ensure a safe switch-off in case of a fault!  If required increase the power of the transformer to reach the necessary short circuit capability.   ■  A low cost alternative to screened (shielded) motor cables is the use of NYCY or NYCWY cables (power cables with concentric  protective conductor).  Failure to follow these instructions will result in death or serious injury.        Cable cross sections      Mains supply  Motor output      No. of  phases  Pre-fuse  (per  phase)  Recommended  cable [mm²]  Max. cable  [mm²]  (per phase)   Internal fuse  (per phase)  Max. cable  (without motor  choke) [mm²]   (per phase)  Max. cable   (with motor  choke) [mm²]  (per phase)  Recommended  cable [mm²]  ATV61EX●●  D55N4H  3  160 A  1x (3x 70)  1x 95 (M6)  160 A sf  1x 50 (M6)  1x 50 (M6)  1x (3x 50)   D75N4H  3  200 A  1x (3x 95)  2x 185 (M12)  200 A sf  1x 150 (M10)  1x 150 (M10)  1x (3x 70)   D90N4H  3 250A   1x (3x 120)   2x 185 (M12)  250 A sf  1x 150 (M10)  1x 150 (M10)  1x (3x 95)    C11N4H  3 250A   1x (3x 120)   2x 185 (M12)  250 A sf  1x 150 (M10)  1x 150 (M10)  1x (3x 120)    C13N4H  3 315A   1x (3x 185)   2x 185 (M12)  315 A sf  2x 185 (M12)   2x 185 (M12)   1x (3x 150)    C16N4H  3 400A   2x (3x 120)   2x 150 (M10)  400 A sf  2x 185 (M12)   2x 185 (M12)   2x (3x 95)    C22N4H  3 500A   2x (3x 150)   2x 150 (M10)   500 A sf  2x 185 (M12)   2x 185 (M12)   2x (3x 120)    C25N4H  3 630A   2x (3x 185)   2x 300 (M10)  1)   550 A sf  2x 240 (M12)   2x 240 (M12)   2x (3x 150)    C31N4H  3 800A   3x (3x 185)   3x 185 (M12)   700 A sf  2x 240 (M12)   2x 240 (M12)   3x (3x 150)    C40N4H  3 1000A   4x (3x 185)   4x 300 (M12)   2x 500 A sf  4x 240 (M12)   4x 240 (M12)  3x (3x 185)    C50N4H  3 1250A   4x (3x 240)   4x 300 (M12)   2x 550 A sf  4x 240 (M12)   4x 240 (M12)  4x (3x 185)    C63N4H  3 1600A   6x (3x 240)   6x 300 (M12)  1)   2x 700 A sf  6x 240 (M12)   6x 240 (M12)  5x (3x 185)     1) .......... Connection only with special cable lugs for switching devices possible    NOTICE   Differing cable cross sections on request.      

Connection    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V       42                   Cable cross sections at cable entry via the top      Mains supply  Motor output      No. of  phases  Pre-fuse  (per  phase)  Recommended  cable [mm²]  Max. cable  [mm²]  (per phase)   Internal fuse  (per phase)  Max. cable  (without motor  choke) [mm²]   (per phase)  Max. cable   (with motor  choke) [mm²]  (per phase)  Recommended  cable [mm²]  ATV61EX●●  D55N4H  - -  -  -  -  -  -  -   D75N4H  3  200 A  1x (3x 95)  1x 150 (M10)  200 A sf  1x 150 (M10)  1x 150 (M10)  1x (3x 70)   D90N4H  3 250A   1x (3x 120)   1x 150 (M10)  250 A sf  1x 150 (M10)  1x 150 (M10)  1x (3x 95)    C11N4H  3 250A   1x (3x 120)   1x 150 (M10)  250 A sf  1x 150 (M10)  1x 150 (M10)  1x (3x 120)    C13N4H  3 315A   1x (3x 185)   2x 185 (M12)   315 A sf  2x 185 (M12)   2x 185 (M12)   1x (3x 150)    C16N4H  3 400A   2x (3x 120)   2x 185 (M12)   400 A sf  2x 185 (M12)   2x 185 (M12)   2x (3x 95)    C22N4H  3 500A   2x (3x 150)   2x 185 (M12)   500 A sf  2x 185 (M12)   2x 185 (M12)   2x (3x 120)    C25N4H  3 630A   2x (3x 185)   4x 240 (M12)   550 A sf  4x 240 (M12)   4x 240 (M12)   2x (3x 150)    C31N4H  3 800A   3x (3x 185)   4x 240 (M12)   700 A sf  4x 240 (M12)   4x 240 (M12)   3x (3x 150)    C40N4H  3 1000A   4x (3x 185)   4x 240 (M12)  2x 500 A sf  4x 240 (M12)   4x 240 (M12)  3x (3x 185)    C50N4H  3 1250A   4x (3x 240)   4x 240 (M12)  2x 550 A sf  4x 240 (M12)   4x 240 (M12)  4x (3x 185)    C63N4H  3 1600A   6x (3x 240)   6x 240 (M12)  2x 700 A sf  6x 240 (M12)   6x 240 (M12)  5x (3x 185)     1) ..........Connection only with special cable lugs for switching devices possible    NOTICE   Differing cable cross sections on request.      

Connection    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V                       43         Motor cable lengths  Because of the permitted mains disturbances, the allowed overvoltages at the motor, the occurring bearing currents and the permitted losses the distance between inverter and motor(s) is limited. The maximum distance heavily depends on the type of motor cable (screened/unscreened) as well as from the used options.    Overvoltages at the motor  Overvoltages at the motor terminals result from reflection in the motor cable. Basically the motors are stressed with measurable higher voltage peaks from a motor cable length of 50 m. Thereby the motor load is nearly independent from the used inverter !  Line supply voltage 400 V  Motor insulation for 1300 V phase-to-phase peak voltage and dv/dt resistance  8 kV/μs  In order to use standard motors in this voltage range, the Altivar frequency inverters have a function to inhibit short output voltage pulses. With this function the reflection conditional overvoltages are attenuated. The slew rate as well as the EMC load are not influenced by changing this parameter.  At even longer motor cables the use of a "dv/dt filter" is required. Combined with the cable capacitance the option motor choke affects like a filter and limits the voltage peaks at the motor as well as the slew rate of the output pulses.    When the specified motor cable lengths are observed the motor life time can be significantly extended.  Line supply voltage 400 V  max. 1000 V phase-to-phase peak voltage and dv/dt 500 V/μs    CAUTION  RISK OF OVERVOLTAGE AT THE MOTOR Observe the specified length of motor cables in order to protect the motor !  Failure to follow these instructions can result in equipment damage.    EMC interferences  The Altivar 61 Plus-LH causes high-frequent interferences which drain off more and more stronger to the earth potential with increasing motor cable length. As a result the line-conducted interferences to the mains increase. The attenuation of the line reactors is not longer sufficient and the permitted interference limits are exceeded.    NOTICE  Observing the specified length of motor cables is also necessary for compliance with the EMC limits.    Bearing currents  Common mode bearing currents which even cannot be prevented by means of motors equipped with an insulated bearing are significantly reduced by use of the option motor choke.  Especially in case of big motors with middle up to high motor cable lengths the option motor choke is considerable to increase the availability of the motor. 

Connection    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V       44                      Multiplication factors    In case of different conditions the recommended cable lengths must be converted by means of the following factors.  If several factors apply, please multiply them.    ■  The pulse frequency does not correspond to factory default:    at 4 kHz  multiply all values by 0.7  at 8 kHz  multiply all values by 0.4    ■  In case of output frequencies higher than 100 Hz:  up to 200 Hz  multiply all values by 0.8  up to 300 Hz  multiply all values by 0.5    ■  Instead of two parallel cables one thicker cable is used:  multiply all values by 1.5    ■  In case of 6-pole motor cabling (e.g. for star/delta starting circuit):  multiply all values by 0.75    ■  In case of parallel motors with their centre near the inverter values must be converted in compliance with the number of motors.  When an adjusted motor choke is used for each motor, the following values in brackets apply.    at 2 motors  multiply all values by 0.40 (0.80)  at 3 motors  multiply all values by 0.25 (0.60)  at 4 motors  multiply all values by 0.15 (0.40)  at 5 motors  multiply all values by 0.10 (0.25)    ■  If the centre of the parallel motors is near the motors, following factors for conversion apply:    at 2 motors  multiply all values by 0.80  at 3 motors  multiply all values by 0.60  at 4 motors  multiply all values by 0.40  at 5 motors  multiply all values by 0.25    Recommended maximum lengths of motor cables in 2 nd  environment (industrial environment)  C3 (EN 55011 - class A group 2) no option  )  50 m  screened cable  with motor choke  80 m  screened cable  C4 (EMC concept) no option )  100 m  screened cable  with motor choke  300 m  screened cable  no option )  150 m  unscreened cable  with motor choke  300 m  unscreened cable    )  By means of a software function to inhibit short output voltage pulses the overvoltage at the motor terminals is limited to the double DC voltage. Before you can use this function you have to ensure that the motor is suitable!    NOTICE  The specified lengths of motor cables are recommended limits based on typical motor cables, laying in cable channels, default pulse frequency and maximal output frequency of 100 Hz. 

Options    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V                       45         Options    Available options  To enlarge the field of applications, various options are available concerning control and operation, extensions referring to the electric arrangement and to increase the protection degree.    General enclosure options  Allocation table for options  Option  Brief description  Order number  Weight  [kg]  Reference  Inputs/outputs Basic I/O extension card   Terminal extension for additional logic inputs and outputs  VW3 A3E 201  0.320  See product  catalogue  Extended I/O extension card   Terminal extension for additional analog and logic inputs and outputs  VW3 A3E 202  0.300  See product  catalogue  Control terminals X12   Control terminals for the basic inverter  VW3 AE 1201  0.700  page 51  Control terminals X12, X13   Control terminals for the basic device and the I/O option cards  VW3 A3E 201 and 202.  VW3 AE 1202  0.900  page 51  Adapter for 115 V logic inputs  Enables the use of 115 V logic signals.  VW3 A3E 101  0.200  See product  catalogue  Relay output OC  Relay for logic output (Open collector)  VW3 AE 2201  0.100  page 52  Multi-pump card   Allows the adaptation to pump applications.  VW3 A3E 502  0.320  See product  catalogue  Extended multi-pump card   This card supports all multi-pump applications.  VW3 A3E 503  0.320  See product  catalogue  "Controller inside" card   Programmable card for integration of control system functions.  VW3 A3E 501  0.300  See product  catalogue  Additional electrical input isolation   Isolated amplifier with optoelectronic potential separation connected to the analog input of the inverter  VW3 AE 1901  0.100  page 53  Additional electrical output isolation  Isolated amplifier with optoelectronic potential separation connected to the analog output of the inverter  VW3 AE 1902  0.100  page 54  Encoder feedback Encoder interface card  5 V / RS422  Extension card for encoder feedback.  Supply voltage 5 V / RS422  VW3 A3E 401  0.200  Encoder interface card  12 V OC  Extension card for encoder feedback.  Supply voltage 12 V / open collector output  VW3 A3E 403  0.200  Encoder interface card  15 V OC  Extension card for encoder feedback.  Supply voltage 15 V / open collector output  VW3 A3E 404  0.200  Encoder interface card  12 V (push-pull)  Extension card for encoder feedback.  Supply voltage 12 V / push-pull  VW3 A3E 405  0.200  Encoder interface card  15 V (push-pull)  Extension card for encoder feedback.  Supply voltage 15 V / push-pull  VW3 A3E 406  0.200  Encoder interface card  24 V (push-pull)  Extension card for encoder feedback.  Supply voltage 24 V / push-pull  VW3 A3E 407  0.200  See  product    catalo g ue  Fieldbuses (buildings) LonWorks communication card  Option card for control of the inverter via LonWorks.  VW3 A3E 312  0.300  METASYS N2 communication card  Option card for control of the inverter via METASYS N2.  VW3 A3E 313  0.300  APOGEE FLN communication card  Option card for control of the inverter via APOGEE FLN.  VW3 A3E 314  0.300  BACnet communication card  Option card for control of the inverter via BACnet.  VW3 A3E 315  0.300  See  product    catalo g ue 

Options    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V       46                   Allocation table for options  Option  Brief description  Order number  Weight  [kg]  Reference  Fieldbuses (industry) Modbus TCP Daisy Chain communication card  Option card for control of the inverter via Modbus TCP Daisy Chain.  VW3 A3E 310D  0.300  Ethernet/IP communication card  Option card for control of the inverter via Ethernet/IP.  VW3 A3E 316  0.300  Fipio communication card  Option card for control of the inverter via Fipio.  VW3 A3E 311  0.300  Modbus Plus communication card  Option card for control of the inverter via Modbus plus.  VW3 A3E 302  0.300  DeviceNet communication card  Option card for control of the inverter via DeviceNet.  VW3 A3E 309  0.300  Interbus communication card  Option card for control of the inverter via Interbus.  VW3 A3E 304  0.300  CC-Link communication card  Option card for control of the inverter via CC-Link.  VW3 A3E 317  0.300  Modbus/Uni-Telway communication card  Option card for control of the inverter via Modbus/Uni-Telway.  VW3 A3E 303  0.300  Profibus DP communication card  Option card for control of the inverter via Profibus DP.  VW3 A3E 307  0.300  Profibus DPv1 communication card  Option card for control of the inverter via Profibus DPv1.  VW3 A3E 307 S371  0.300  See  product    catalo g ue  Safety - monitoring of the motor Emergency stop button  VW3 AE 1501  0.100  page 58  "Preventa type AC" fault relay  VW3 AE 1502  0.100  page 58  "Preventa type ATE" fault relay  This function prevents any unintended start-up of the motor and guarantees the safety of the machine and plant personnel.  VW3 AE 1503  0.100  page 60  PTC relay  PTC thermistor relay to monitor the PTC thermistors in the motor  VW3 AE 2001  0.100  page 55  PTC relay with PTB (ATEX) certification  PTC thermistor relay with PTB certificate to monitor the PTC thermistors in the motor in EX-environments  VW3 AE 2002  0.100  page 56  Pt100 relay  for motor winding  Pt100 relay to monitor Pt100 sensors in the motor winding  VW3 AE 2003  0.300  page 56  Pt100 relay  for motor bearings  Pt100 relay to monitor Pt100 sensors in the motor bearings  VW3 AE 2004  0.300  page 57  Pt100 relay for transformer  Pt100 relay to monitor Pt100 sensors in the transformer  VW3 AE 2005  0.300  page 57  Further enclosure options Insulation monitoring  Monitors each phase to earth fault (only for IT networks)  VW3 AE 2601  5.000  page 61  Design for IT networks  The frequency inverter is prepared for connection to nongrounded networks (IT networks).  VW3 AE 2701  −  page 61  External 230V AC supply terminals  Provides the terminals and the protection for an external 230 V supply voltage.  VW3 AE 1301  0.100  page 62  External 24 V DC supply terminals  Provides the terminals and the protection for an external 24 V buffer voltage.  VW3 AE 1402  0.100  page 62  Enclosure lighting  Fluorescent lamp and a power socket 230V AC  VW3 AE 1601  1.500  page 63  Key switch  (Local / Remote)  Key switch in the enclosure door for switching between terminals/bus and local operation  VW3 AE 1801  0.200  page 64  Motor heating   Includes a circuit breaker, a contactor and the terminals to connect a motor heating  VW3 AE 2101  0.200  page 63  External motor fan  Includes a circuit breaker, a contactor and the terminals to connect an external motor fan  VW3 AE 2102  0.200  page 64  Voltmeter 400 V  Measuring instrument built-in in the enclosure door, which indicates the line voltage.  VW3 AE 2301  0.400  page 64    NOTICE   For enclosure design ATV61EXC ●D55N4H the general enclosure options are only available on request.     

Options    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V                       47        Enclosure options depending on the power  Option  Brief description  Reference  Isolating handle for switch  Enables handling without opening the enclosure door  Page 65   Circuit breaker  Provides a safe switching-off at overload  Page 66   Door handle for circuit breaker  Enables handling without opening the enclosure door  Page 65   Undervoltage coil 230 V  When there is no voltage at the undervoltage coil, the circuit breaker switches off.  Page 66   Undervoltage coil 110 V  When there is no voltage at the undervoltage coil, the circuit breaker switches off.  Page 67   230 V motor for circuit breaker  Remote control of the circuit breaker via control commands is possible by means of this motor drive.  Page 67   110 V motor for circuit breaker  Remote control of the circuit breaker via control commands is possible by means of this motor drive.  Page 67   Ammeter  Measuring instrument built-in in the enclosure door, which indicates the line current.  Page 68   Enclosure heater  Heats the enclosure to avoid frost and condensation up to an ambient temperature of -10°C  Page 68   Motor choke  Reduces the slew rate on the output of the inverter to protect the motor  Page 69   Cable entry via the top  Allows connection of the line and the motor cables from above  Page 70  Enclosure plinth  200 mm plinth  Page 71       Allocation table for options depending on the power  Description  ATV61  Order number  Weight [kg]  Isolating handle for switch  EXC ●D55N4H  VW3 AE 0190  0.500    EXC ●D75N4H…C13N4H  VW3 AE 0103  1.000    EXC ●C16N4H…C31N4H  VW3 AE 0104  2.000     EXC ●C40N4H...C63N4H  VW3 AE 0105   2.000  Circuit breaker  EXC ●D55N4H  −  −    EXC ●D75N4H  VW3 AE 0141  0.500    EXC ●D90N4H…C13N4H  VW3 AE 0142  −    EXC ●C16N4H  VW3 AE 0146  1.400    EXC ●C22N4H, C25N4H  VW3 AE 0147  1.400    EXC ●C31N4H  VW3 AE 0148  1.400    EXC ●C40N4H, C50N4H  VW3 AE 0151  −     EXC ●C63N4H  VW3 AE 0169  −  Door handle for circuit breaker  EXC ●D55N4H  −  −    EXC ●D75N4H...C13N4H  VW3 AE 0114  1.000    EXC ●C16N4H…C31N4H  VW3 AE 0115  2.000     EXC ●C40N4H...C63N4H  VW3 AE 0116  2.000  Undervoltage coil 230 V  EXC ●D55N4H  −  −    EXC ●D75N4H...C31N4H  VW3 AE 0117  0.500     EXC ●C40N4H…C63N4H  VW3 AE 0118  0.500  Undervoltage coil 110 V  EXC ●D55N4H  −  −    EXC ●D75N4H...C31N4H  VW3 AE 0119  0.500     EXC ●C40N4H…C63N4H  VW3 AE 0120  0.500  230 V motor for circuit breaker  EXC ●D55N4H  −  −    EXC ●D75N4H  VW3 AE 0154  1.000    EXC ●D90N4H…C13N4H  VW3 AE 0155  1.000    EXC ●C16N4H  VW3 AE 0156  3.000    EXC ●C22N4H...C31N4H  VW3 AE 0157  3.000    EXC ●C40N4H, C50N4H  VW3 AE 0159  7.000     EXC ●C63N4H  VW3 AE 0176  7.000  110 V motor for circuit breaker  EXC ●D55N4H  −  −    EXC ●D75N4H  VW3 AE 0160  1.000    EXC ●D90N4H…C13N4H  VW3 AE 0161  1.000    EXC ●C16N4H  VW3 AE 0162  3.000    EXC ●C22N4H...C31N4H  VW3 AE 0163  3.000    EXC ●C40N4H, C50N4H  VW3 AE 0165  7.000     EXC ●C63N4H  VW3 AE 0179  7.000 

Options    Altivar 61 Plus-LH    ATV61EX ●●●●●N4H  Line supply voltage 400 V       48                   Allocation table for options depending on the power  Description  ATV61  Order number  Weight [kg]  Ammeter  EXC ●D55N4H  −  −    EXC ●D75N4H, D90N4H  VW3 AE 0404  0.200    EXC ●C11N4H…C16N4H  VW3 AE 0406  0.200    EXC ●C22N4H…C31N4H  VW3 AE 0426  0.200    EXC ●C40N4H...C50N4H  VW3 AE 0409  0.200     EXC ●C63N4H  VW3 AE 0427  0.200  Enclosure heater  EXC ●D55N4H  −  −    EXC ●D75N4H…C31N4H  VW3 AE 0501  0.500      EXC ●C40N4H…C63N4H  VW3 AE 0502  1.000  Motor choke  EXC ●D55N4H…D90N4H  VW3 AE 0603  17.000    EXC ●C11N4H, C13N4H  VW3 AE 0604  35.000    EXC ●C16N4H, C22N4H  VW3 AE 0605  64.000    EXC ●C25N4H, C31N4H  VW3 AE 0606  102.000    EXC ●C40N4H  VW3 AE 0608  222.000    EXC ●C50N4H  VW3 AE 0609  228.000      EXC ●C63N4H  VW3 AE 0610  234.000  Cable entry via the top  Without motor choke  EXC ●D55N4H  −  −      EXC ●D75N4H  VW3 AE 0742  108.000      EXC ●D90N4H  VW3 AE 0743  108.000      EXC ●C11N4H  VW3 AE 0744  108.000      EXC ●C13N4H, C16N4H  VW3 AE 0706  108.000      EXC ●C22N4H  VW3 AE 0707  108.000      EXC ●C25N4H, C31N4H  VW3 AE 0708  126.000      EXC ●C40N4H  VW3 AE 0709  216.000      EXC ●C50N4H  VW3 AE 0710  252.000      EXC ●C63N4H  VW3 AE 0711  252.000   With  motor  choke  EXC ●D55N4H  −  −      EXC ●D75N4H  VW3 AE 0742  108.000      EXC ●D90N4H  VW3 AE 0743  108.000      EXC ●C11N4H  VW3 AE 0744  108.000      EXC ●C13N4H, C16N4H  VW3 AE 0706  108.000      EXC ●C22N4H  VW3 AE 0707  108.000      EXC ●C25N4H, C31N4H  VW3 AE 0708  126.000      EXC ●C40N4H  VW3 AE 0712  108.000      EXC ●C50N4H  VW3 AE 0713  126.000        EXC ●C63N4H  VW3 AE 0714  126.000  Enclosure plinth 200 mm  Without motor choke  EXC ●D55N4H  VW3 AE 0807  9.000      EXC ●D75N4H…C11N4H  VW3 AE 0801  11.000      EXC ●C13N4H, C16N4H  VW3 AE 0802  13.000      EXC ●C22N4H  VW3 AE 0827  22.000      EXC ●C25N4H, C31N4H  VW3 AE 0828  26.000      EXC ●C40N4H, C50N4H  VW3 AE 0829  30.000      EXC ●C63N4H  VW3 AE 0830  34.000   With  motor  choke  EXC ●D55N4H  VW3 AE 0807  9.000      EXC ●D75N4H…C11N4H  VW3 AE 0801  11.000      EXC ●C13N4H, C16N4H  VW3 AE 0802  13.000      EXC ●C22N4H  VW3 AE 0827  22.000      EXC ●C25N4H, C31N4H  VW3 AE 0828  26.000      EXC ●C40N4H, C50N4H  VW3 AE 0831  39.000        EXC ●C63N4H  VW3 AE 0832  43.000  Additional enclosure plinth   Without motor choke  EXC ●D55N4H  −  −  for cable entry via the top    EXC ●D75N4H…C31N4H  VW3 AE 0807  9.000      EXC ●C40N4H...C63N4H  VW3 AE 0808  18.000   With  motor  choke  EXC ●D55N4H  −  −      EXC ●D75N4H…C31N4H  VW3 AE 0807  9.000       EXC ●C40N4H…C63N4H  VW3 AE 0809  9.000 

Wiring diagram    Altivar 61 Plus-LH    Wiring and connection                        49       Wiring and connection      Wiring diagram    Wiring diagram        MS.................................... Main switch built-in as standard   (to be used if required according to the local regulations)  Option CB ........................ Circuit breaker  Can be installed instead of the main switch  NH .................................... Main fuses built-in as standard considering table "chapter "Fuses and cable cross sections" " 230 V ................................ Control transformer 230 V AC 24 V .................................. 24 V DC power supply LC..................................... Integrated line contactor EMC ................................. Integrated radio frequency interference filter  considering category C3 according to EN 61800-3 "Use in industrial environments"  LFC................................... Line Filter Choke AIC ................................... Active Infeed Converter INV ................................... Inverter ATV61 Opt. motor choke............. To reduce the voltage peaks at the motor in case of long motor cables 

Wiring diagram    Altivar 61 Plus-LH    Wiring and connection        50                    

Cubicle options    Altivar 61 Plus-LH    Options                        51       Options      Cubicle options    Control terminals X12 for the basic device          The signal inputs  and outputs of the frequency inverter are wired to thecustomer terminals X12 with plug connection (max. cable cross section:2.5 mm 2 ).                Order number: VW3 AE 1201    A1 ................... Frequency inverter ATV61  A2 ................... Enclosure     NOTICE   This option is built in as standard at enclosure design ATV61EXC ●D55N4H.      Control terminals X12 and X13 for the basic device and I/O extension cards          The signal inputs and outputs of the frequency inverter and of the optioncards are wired to the customer terminals X12 and X13 with plugconnection (max. cable cross section: 2.5 mm 2 ).                Order number: VW3 AE 1202    A1 .................... Frequency inverter ATV61  A2 .................... Enclosure   A3 .................... Basic I/O extension card  A4 .................... Extended I/O extension card       

Cubicle options    Altivar 61 Plus-LH    Options        52                   Relay output OC  This option contains a 24 V DC relay with a switching capacity of max. 6 A at 250 V AC or 30 V DC. The potential-free signal outputs are directly connected to the customer control terminals X14 (max. cable cross section: 4 mm 2 ). The inductor is wired to the logic output of the frequency inverter.  With this option each logic status information of the inverter or the process can be issued as a message by means of a logic output.     Relay output LO1  12 14 11 A2 A1 X14.23 X14.22 X14.21 A2 0 V LO1 A3   Order number: VW3 AE 2201    A2 .....................................Enclosure   A3 .....................................Relay    This option requires a basic I/O extension card!        Relay output LO2  12 14 11 A2 A1 X14.26 X14.25 X14.24 A2 0 V LO2 A3   Order number: VW3 AE 2201    A2 .....................................Enclosure   A3 .....................................Relay    This option requires a basic I/O extension card!        Relay output LO3  12 14 11 A2 A1 X14.29 X14.2 8 X14.27 A2 0 V LO3 A3   Order number: VW3 AE 2201    A2 .....................................Enclosure   A3 .....................................Relay    This option requires an extended I/O extension card!        Relay output LO4  12 14 11 A2 A1 X14.32 X14.31 X14.30 A2 0 V LO4 A3   Order number: VW3 AE 2201    A2 .....................................Enclosure   A3 .....................................Relay  This option requires an extended I/O extension card!     

Cubicle options    Altivar 61 Plus-LH    Options                        53         Additional electrical input isolation  This option contains an isolated amplifier configured for an analog input. The signal inputs of the amplifier are directly connected to the customer control terminals X14 (max. cable cross section: 4 mm 2 ). The output is  wired to the analog input of the frequency inverter. It operates according to the principle of optoelectronic potential separation and has three-way separation between input, output and supply.     Analog input AI2  V o OPG IPG Ii A2 A1 X14.12 X14.1 1 A2 0 V 0 - 20 mA4 - 20 mA + 24 V COM AI2 A3   Order number: VW3 AE 1901    A2 .....................................Enclosure   A3 .....................................Isolated amplifier     

Cubicle options    Altivar 61 Plus-LH    Options        54                     Additional electrical output isolation  This option contains an isolated amplifier configured for an analog output. The signal outputs of the amplifier are directly connected to the customer control terminals X14 (max. cable cross section: 4 mm 2 ). The input is wired  to the analog output of the frequency inverter. It operates according to the principle of optoelectronic potential separation and has three-way separation between input, output and supply.      Analog output AO1  V o OPG IPG Ii A2 A1 X1 4. 14 X1 4. 13 A2 0 V + 24 V COM AO1 A3 0-20 mA4-20 mA   Order number: VW3 AE 1902    A2 .....................................Enclosure   A3 .....................................Isolated amplifier        Analog output AO2  A2 A1 X1 4. 16 X1 4. 15 A2 0 V + 24 V COM AO2 A3 0-20 mA4-20 mA V o OPG IPG Ii   Order number: VW3 AE 1902    A2 .....................................Enclosure   A3 .....................................Isolated amplifier    This option requires an extended I/O extension card!        Analog output AO3  A1 X1 4. 18 X1 4. 17 A2 0 V + 24 V COM AO3 A3 0-20 mA4-20 mA A2 V o OPG IPG Ii   Order number: VW3 AE 1902    A2 .....................................Enclosure   A3 .....................................Isolated amplifier    This option requires an extended I/O extension card!       

Cubicle options    Altivar 61 Plus-LH    Options                        55         PTC relay  This option consists of a PTC thermistor relay to monitor the PTC thermistors of the motor. Up to three PTC sensors can be connected to this option. The output of the PTC thermistor relay is assigned to the inverter terminals which can be parameterized for alarm or trip. The thermistor input is wired to the customer terminals X03 (max. cable cross section: 4 mm 2 ).    96 98 95 8 6 5 Y1 Y2 T2 T1 A2 A1 X03.22 X03.21 A2 A3 L N + 24 V ~ 230 V 50 Hz Logic input: External fault   Order number: VW3 AE 2001    A2 .....................................Enclosure   A3 .....................................PTC relay     

Cubicle options    Altivar 61 Plus-LH    Options        56                     PTC relay with PTB (ATEX) certification  This option consists of a PTC thermistor relay with PTB certificate for operation in EX-environments to monitor the PTC thermistors of the motor. Up to three PTC sensors can be connected to this option. The output of the PTC thermistor relay is assigned to the inverter terminals (PWR). The thermistor input is wired to the customer terminals X03 (max. cable cross section: 4 mm 2 ).    22 24 21 14 12 11 X1 X2 P2 P1 A2 A1 X03.91 X03.90 A2 A3 L N + 24 V ~ 230 V 50 Hz + 24 V PWR Logic input: External fault   Order number: VW3 AE 2002    A2 .....................................Enclosure   A3 .....................................PTC relay        Pt100 relay          Pt100 sensors in motor winding          This option contains a Pt100 relay to monitor the Pt100 sensors of the motor. As standard it is prepared for three sensors for the windings. The alarm message is assigned to the terminals and the trip will cause a trip shut-down at the inverter. The input for the sensors, the alarm relay and the analog output are wired to the customer terminals X03 (max. cable cross section: 4 mm 2 ).        32 34 31 24 22 21 5 6 4 3 9 10 8 7 2 1 X03.10 X03.9 X03. 8 X03.7 X03.6 X03.5 X03.4 X03.3 X03.2 X03.1 A2 A3 +2 4V +2 4V 0V 14 12 11 0-20 mA4-20 mA Logic input: External fault Alarm   Order number: VW3 AE 2003    A2 .....................................Enclosure   A3 .....................................Pt100 relay     

Cubicle options    Altivar 61 Plus-LH    Options                        57         Pt100 sensors in bearings          This option contains a Pt100 relay to monitor the Pt100 sensors of themotor.  As standard it is prepared for two sensors for the bearings. Thealarm message is assigned to the terminals and the trip will cause a tripshut-down at the inverter. The input for the sensors, the alarm  relay andthe analog output are wired to the customer terminals X03 (max. cablecross section: 4 mm 2 ).        32 34 31 24 22 21 5 6 4 3 9 10 8 7 2 1 X03.20 X03.19 X03.1 8 X03.17 X03.16 X03.15 X03.14 X03.13 X03.12 X03.1 1 A2 A3 +2 4V +2 4V 0V 14 12 11 0-20 mA4-20 mA Logic input: External fault Alarm   Order number: VW3 AE 2004    A2 .....................................Enclosure   A3 .....................................Pt100 relay            Pt100 sensors in the transformer          This option contains a Pt100 relay to monitor the Pt100 sensors in thetransformer. As standard it is prepared for three sensors for the windings.The alarm message is assigned to the terminals and the trip will cause atrip shut-down at the inverter. The input for the sensors, the alarm relayand the analog output are wired to the customer terminals X03 (max. cablecross section: 4 mm 2 ).        32 34 31 24 22 21 5 6 4 3 9 10 8 7 2 1 X03.60 X03.59 X03.5 8 X03.57 X03.56 X03.55 X03.54 X03.53 X03.52 X03.51 A2 A3 +2 4V +2 4V 0V 14 12 11 0-20 mA4-20 mA Logic input: External fault Alarm   Order number: VW3 AE 2005    A2 .....................................Enclosure   A3 .....................................Pt100 relay     

Cubicle options    Altivar 61 Plus-LH    Options        58                       Safe Standstill  The Altivar   frequency inverters include the “Safe Standstill" (Power  Removal) safety function as standard. This function prevents any unintended start-up of the motor and guarantees the safety of the machine and plant personnel. The Safe Standstill function is wired to the customer terminals X11 (max. cable cross section: 4 mm 2 ).    Safety category 1  Stop category 0  according to EN 954-1 / ISO 13849-1 category 1; IEC/EN 61508, SIL1 according to IEC/EN 60204-1  Emergency stop button    PA /+ W /T3 PO PC /– U /T1 V /T2 AI2 AI1– AO1 CO M CO M +10 V AI1+ R /L1 S /L2 T /L3 R1A R1C R1B LI1 LI2 LI3 LI4 +2 4V PWR LI5 LI6 A1 R2A R2C X1 1.7 X1 1. 8 X1 1.5 X1 1.6 A3 A2 L1 L2 L3 Q1 F1 IL1 S2 S1   Order number: VW3 AE 1501    A1 ....................Frequency inverter ATV61  A2 ....................Enclosure   A3 ....................Emergency stop wiring   S1 ....................Emergency stop button consisting of  Mushroom head pushbutton (Harmony style 4: ZB4 BS54) Auxiliary contact (Harmony style 4: ZB4 BZ102) 

Cubicle options    Altivar 61 Plus-LH    Options                        59     Safety category 3  Stop category 0  according to EN 954-1 / ISO 13849-1 category 3; IEC/EN 61508, SIL2 according to IEC/EN 60204-1  "Preventa type AC" fault relay    PA /+ W /T3 PO PC /– U /T1 V /T2 AI2 AI1– AO1 CO M CO M +1 0 AI1+ R /L1 S /L2 T /L3 R1A R1C R1B LI1 LI2 LI3 LI4 +2 4 PWR LI5 LI6 A1 R2A R2C A3 A1 Y1 13 23 33 Y43 14 24 34 Y44 + – A2 48 V, 115 V, 230 V PE K1 K1 K2 K2 T Y2 XPS AC A2 X1 1.5 X1 1.6 X1 1.7 X1 1. 8 X1 1.9 X1 1.10 S1 S2 L1 L2 L3 Q1 F1 IL1 L1 (+) 24 V A C /DC NC (–) F2 ESC A4 S3     Order number: VW3 AE 1502    A1 ..................................... Frequency inverter ATV61  A2 ..................................... Enclosure   A3 ..................................... Safety switching device "Preventa XPS-AC5121"  A4 ..................................... Emergency stop button (VW3 AE 1501)  S3 ..................................... Emergency stop button consisting of  Mushroom head pushbutton (Harmony style 4: ZB4 BS54) Auxiliary contact (Harmony style 4: ZB4 BZ102)       

Cubicle options    Altivar 61 Plus-LH    Options        60                   Safety category 3  Stop category 1  according to EN 954-1 / ISO 13849-1 category 3; IEC/EN 61508, SIL2 according to IEC/EN 60204-1  "Preventa type ATE" fault relay    PA /+ W /T3 PO PC /– U /T1 V /T2 AI2 AI1– AO1 CO M CO M +1 0 AI1+ R /L1 S /L2 T /L3 R1A R1C R1B LI1 LI2 LI3 LI4 +2 4 PWR LI5 LI6 A1 R2A R2C S21 S11 A1 A2 PE Y1 13 T – + 115 V 230 V 2 K2 K1 K3K4 K1 K2 K3 23 24 14 78 68 58 57 Y + Y88 67 77 B1 S12 S22 S33 ESC XPS ATE Y2 Y3 S2 K4 K1 K2 K2 K1 K4 K3 1 Y4 Y5 A3 A2 X1 1.6 X1 1. 8 X1 1.7 X1 1.5 X11.9 X11.10 S1 S3 L1 (+) NC (–) F2 L1 L2 L3 Q1 F1 IL1 A4 24 V AC/DC     Order number: VW3 AE 1503    A1 ..................................... Frequency inverter ATV61  A2 ..................................... Enclosure   A3 ..................................... Safety switching device "Preventa XPS-ATE5110"  A4 ..................................... Emergency stop button (VW3 AE 1501)  S3 ..................................... Emergency stop button consisting of  Mushroom head pushbutton (Harmony style 4: ZB4 BS54) Auxiliary contact (Harmony style 4: ZB4 BZ102)   

Cubicle options    Altivar 61 Plus-LH    Options                        61         Insulation monitoring for IT networks  This option monitors each phase to earth fault.  This option is only qualified for IT networks.     PA /+ W /T3 PO PC /– U /T1 V /T2 AI2 AI1– AO1 CO M CO M +1 0 AI1+ R /L1 S /L2 T /L3 R1A R1C R1B LI1 LI2 LI3 LI4 +2 4 PWR LI5 LI6 A1 R2A R2C A2 L1 L2 L3 Q1 F1...F3 X03.35 X03.34 X03.33 R 17 18 7 4 19 10 37 R 13 14 15 L1 N A3 22 21 20     A1 .................Frequency inverter ATV61 A2 .................Enclosure A3 .................Isolation monitoring device   Order number: VW3 AE 2601    The trigger R is connected to the inverter as standard. The alarm message R is wired to the terminals (X3.33 to X3.35).      Design for IT networks  The frequency inverter is prepared for connection to nongrounded networks (IT networks).  Order number: VW3 AE 2701 

Cubicle options    Altivar 61 Plus-LH    Options        62                       Supply voltage 230 V AC          The Altivar 61 Plus-LH already includes a control transformer for 230 V asstandard.  When the control voltage is provided external, the option "external supplyvoltage" has to be selected.            Option external supply terminals          This option includes customer terminals X11 (max. cable cross section:4 mm 2 ) for the connection of an external supply voltage and a circuit breaker with 6 A for protection. The external supply voltage has to bedimensioned for a load from 225 up to 800 VA, depending on the used230 V options.    X1 1. P E X1 1. P E X1 1. 2 X1 1. 1 X1 1.4 X1 1. 3 A2 PE N L ~ 230 V / 50 Hz ~ 230 V / 50 Hz Q1   Order number: VW3 AE 1301    A2 .....................................Enclosure   Q1 .....................................Circuit breaker 6A  X11....................................Customer terminals          External 24 V DC supply terminals          This option includes customer terminals X14 (max. cable cross section:4 mm 2 ) for the connection of an external buffer voltage (min. 2 A) and a circuit breaker with 2 A for protection.     X1 4. 2 X1 4. 1 X1 4.4 X1 4. 3 A2 24 V 0 V + 24 V Q1   Order number: VW3 AE 1402    A2 .....................................Enclosure   Q1 .....................................Circuit breaker 2A  X14....................................Customer terminals     

Cubicle options    Altivar 61 Plus-LH    Options                        63         Enclosure lighting          This option contains a fluorescent lamp and a power socket according toVDE standard (230 V / 50 Hz), a door contact switch and a circuit breaker.The option is wired to the customer terminals X04 (max. cable crosssection: 4 mm 2 ).    NOTICE   This option requires an additional external 230 V supply (min. 1500 VA)! This supply has to be human protected!    X04.PE X04.PE X04.2 X04.1 X04.4 X04.3 A3 A2 PE N L K1 ~ 230 V / 50 Hz (1) (1) (1) Q1 1500 VA min.   Order number: VW3 AE 1601    A2 .....................................Enclosure   A3 .....................................Enclosure lamp  K1 .....................................Door contact  Q1 .....................................Circuit breaker 2A        Motor heating           This option includes the terminals and a contactor for an external motorheating. It allows to connect a motor heater up to 200 W. The output iswired to the customer terminals X03 (max. cable cross section: 4 mm 2 ). The activation takes place by the line contactor or by the inverter. Themotor heating is active when the inverter is in off-state.     A3 A2 Q1 K1 X03.PE X03.32 X03.31 ~ 230 V / 50 Hz L N 200 W max.   Order number: VW3 AE 2101    A2 .....................................Enclosure   A3 .....................................Motor heater  K1 .....................................Contactor  Q1 .....................................Motor circuit breaker     

Cubicle options    Altivar 61 Plus-LH    Options        64                       External motor fan          This option includes the terminals, a contactor and a circuit breaker for an external motor fan. It allows to connect an external motor fan up to1000 W. The output is wired to the customer terminals X03 (max. cablecross section: 4 mm 2 ). The activation takes place by the line contactor or  by the inverter.  The external motor fan is active when the inverter is in operation.     NOTICE   For this option the mains voltage and the voltage of the external fan must be identical. Different voltages on request.       Order number: VW3 AE 2102    A2 .....................................Enclosure   A3 .....................................Protected supply voltage  K1 .....................................Contactor  Q1 .....................................Motor circuit breaker        Key switch „local / remote“    This option includes a key switch built-in the enclosure door, which switches between remote mode (terminals or bus) and panel mode. Thepanel control of the device occurs by means of the keys on the built-in LED-keypad or the removable operation panel, which is also built-in the enclosure door.            Order number: VW3 AE 1801          Voltmeter „Line voltage“    This option indicates the line voltage. It includes a measuring instrumentbuilt-in into the enclosure door and a phase selection switch.            Order number:  ■  Supply voltage 400 V .....................VW3 AE 2301       

Cubicle options  (depending on power)    Altivar 61 Plus-LH    Options                        65          Cubicle options (depending on power)    Door handle for main switch    The main switch is able to switch the supply voltage of the frequencyinverter. The external door handle enables handling of the switch withoutopening the enclosure door.      The main switch is built-in as standard. This option contains only an extended spindle for the door handle.        Allocation table  Description  ATV61  Order number  Weight  [kg]  Isolating handle for switch  400 V  EXC ●D55N4H  VW3 AE 0190  0.500      EXC ●D75N4H…C13N4H  VW3 AE 0103  1.000      EXC ●C16N4H…C31N4H  VW3 AE 0104  2.000       EXC ●C40N4H...C63N4H  VW3 AE 0105   2.000     

Cubicle options  (depending on power)    Altivar 61 Plus-LH    Options        66                       Circuit breaker  I ATV     The circuit breaker is built-in instead of the main switch. It provides a safe switching-off at overload.      Allocation table  Description  ATV61  Order number  Weight  [kg]  Circuit breaker  400 V  EXC ●D55N4H  −  −      EXC ●D75N4H  VW3 AE 0141  0.500      EXC ●D90N4H…C13N4H  VW3 AE 0142  −      EXC ●C16N4H  VW3 AE 0146  1.400      EXC ●C22N4H, C25N4H  VW3 AE 0147  1.400      EXC ●C31N4H  VW3 AE 0148  1.400      EXC ●C40N4H, C50N4H  VW3 AE 0151  −       EXC ●C63N4H  VW3 AE 0169  −        Door handle for circuit breaker      The external door handle enables handling of the switch without openingthe enclosure door.      Allocation table  Description  ATV61  Order number  Weight  [kg]  Door handle for circuit breaker  400 V  EXC ●D55N4H  −  −      EXC ●D75N4H...C13N4H  VW3 AE 0114  1.000      EXC ●C16N4H…C31N4H  VW3 AE 0115  2.000       EXC ●C40N4H...C63N4H  VW3 AE 0116  2.000        Undervoltage coil 230V      When there is no voltage at the undervoltage coil, the circuit breakerswitches off.      Allocation table  Description  ATV61  Order number  Weight  [kg]  Undervoltage coil 230V  400 V  EXC ●D55N4H  −  −      EXC ●D75N4H...C31N4H  VW3 AE 0117  0.500       EXC ●C40N4H…C63N4H  VW3 AE 0118  0.500   

Cubicle options  (depending on power)    Altivar 61 Plus-LH    Options                        67         Undervoltage coil 110V      When there is no voltage at the undervoltage coil, the circuit breakerswitches off.      Allocation table  Description  ATV61  Order number  Weight  [kg]  Undervoltage coil 110V  400 V  EXC ●D55N4H  −  −      EXC ●D75N4H...C31N4H  VW3 AE 0119  0.500       EXC ●C40N4H…C63N4H  VW3 AE 0120  0.500        230V motor for circuit breaker      Remote control of the circuit breaker via control commands is possible bymeans of this motor drive.      Allocation table  Description  ATV61  Order number  Weight  [kg]  230 V motor for circuit breaker  400 V  EXC ●D55N4H  −  −      EXC ●D75N4H  VW3 AE 0154  1.000      EXC ●D90N4H…C13N4H  VW3 AE 0155  1.000      EXC ●C16N4H  VW3 AE 0156  3.000      EXC ●C22N4H...C31N4H  VW3 AE 0157  3.000      EXC ●C40N4H, C50N4H  VW3 AE 0159  7.000       EXC ●C63N4H  VW3 AE 0176  7.000        110V motor for circuit breaker      Remote control of the circuit breaker via control commands is possible bymeans of this motor drive.      Allocation table  Description  ATV61  Order number  Weight  [kg]  110 V motor for circuit breaker  400 V  EXC ●D55N4H  −  −      EXC ●D75N4H  VW3 AE 0160  1.000      EXC ●D90N4H…C13N4H  VW3 AE 0161  1.000      EXC ●C16N4H  VW3 AE 0162  3.000      EXC ●C22N4H...C31N4H  VW3 AE 0163  3.000      EXC ●C40N4H, C50N4H  VW3 AE 0165  7.000       EXC ●C63N4H  VW3 AE 0179  7.000   

Cubicle options  (depending on power)    Altivar 61 Plus-LH    Options        68                       Amperemeter „Line current“      This option indicates the line current. It includes a measuring instrumentbuilt-in into the enclosure door and a current transformer.        Allocation table  Description  ATV61  Order number  Weight  [kg]  Ammeter 400  V  EXC ●D55N4H  −  −      EXC ●D75N4H, D90N4H  VW3 AE 0404  0.200      EXC ●C11N4H…C16N4H  VW3 AE 0406  0.200      EXC ●C22N4H…C31N4H  VW3 AE 0426  0.200      EXC ●C40N4H...C50N4H  VW3 AE 0409  0.200       EXC ●C63N4H  VW3 AE 0427  0.200        Cubicle heating      This option is used to heat the enclosure in order to avoid frost andcondensation up to an ambient temperature of -10°C. It includes the enclosure heating, a thermostat and a circuit breaker. The option is wiredto the customer terminals X04 (max. cable cross section: 4 mm 2 ).      NOTICE  This option requires an additional external 230 V supply (500...1500 VA, depending on the option)! This supply has to be human protected!        X04.PE X04.PE X04.2 X04.1 X04.4 X04.3 A3 A2 PE N L ~ 230 V / 50 Hz J     Allocation table  Description  ATV61  Order number  Weight  [kg]  Enclosure heater  400 V  EXC ●D55N4H  −  −       EXC ●D75N4H…C31N4H  VW3 AE 0501  0.500      EXC ●C40N4H…C63N4H  VW3 AE 0502  1.000   

Cubicle options  (depending on power)    Altivar 61 Plus-LH    Options                        69         Motor choke    ATV     At the output of a voltage source frequency inverter there is a pulsedvoltage with a pulse frequency of 2...16 kHz (ATV61EX ●●●●●N, Y: 2...6 kHz)  and a slew rate of more than 10 kV/ μs.  The use of the option motor choke has significant advantages concerning the trouble-free operation of the drive:  −  Decrease of the voltage load of the motor –recommended from   50 m, necessary from 100 m for 400 V mains supply 10 m, necessary from 30 m for 690 V mains supply  −  Prevention of common mode bearing currents in the motor – especially  important at high power  − Great reduction of the influences to other cables – important if the  separate laying of motor cables cannot be ensured  By means of the especially developed system the voltage drop at the motor choke is negligible small.      Allocation table  Description  ATV61  Order number  Weight   [kg]  Motor choke  400 V  EXC ●D55N4H…D90N4H  VW3 AE 0603  17.000      EXC ●C11N4H, C13N4H  VW3 AE 0604  35.000      EXC ●C16N4H, C22N4H  VW3 AE 0605  64.000      EXC ●C25N4H, C31N4H  VW3 AE 0606  102.000      EXC ●C40N4H  VW3 AE 0608  222.000      EXC ●C50N4H  VW3 AE 0609  228.000      EXC ●C63N4H  VW3 AE 0610  234.000   

Cubicle options  (depending on power)    Altivar 61 Plus-LH    Options        70                       Cable entry above      This option allows the connection of the mains and motor cables from thetop of the enclosure.    NOTICE  For the width of the enclosure in combination with the cable entry via top check out the table in chapter "Width of the cubicle", page 72.        Allocation table  Description  ATV61  Order number  Weight  [kg]  Cable entry via the top  400 V  Without motor choke  EXC ●D55N4H  −  −      EXC ●D75N4H  VW3 AE 0742  108.000      EXC ●D90N4H  VW3 AE 0743  108.000      EXC ●C11N4H  VW3 AE 0744  108.000      EXC ●C13N4H, C16N4H  VW3 AE 0706  108.000      EXC ●C22N4H  VW3 AE 0707  108.000      EXC ●C25N4H, C31N4H  VW3 AE 0708  126.000      EXC ●C40N4H  VW3 AE 0709  216.000      EXC ●C50N4H  VW3 AE 0710  252.000      EXC ●C63N4H  VW3 AE 0711  252.000   With  motor  choke  EXC ●D55N4H  −  −      EXC ●D75N4H  VW3 AE 0742  108.000      EXC ●D90N4H  VW3 AE 0743  108.000      EXC ●C11N4H  VW3 AE 0744  108.000      EXC ●C13N4H, C16N4H  VW3 AE 0706  108.000      EXC ●C22N4H  VW3 AE 0707  108.000      EXC ●C25N4H, C31N4H  VW3 AE 0708  126.000      EXC ●C40N4H  VW3 AE 0712  108.000      EXC ●C50N4H  VW3 AE 0713  126.000       EXC ●C63N4H  VW3 AE 0714  126.000   

Cubicle options  (depending on power)    Altivar 61 Plus-LH    Options                        71         Cubicle plinth 200 mm      There are different additional plinths for the Altivar in IP23 or IP54 design available. Which plinth is necessary depends on the built-in options. Check out the allocation table below. The height of the enclosure will increase of200 mm.        Allocation table  Description  ATV61  Order number  Weight  [kg]  Enclosure plinth  400 V  Without motor choke  EXC ●D55N4H  VW3 AE 0807  9.000      EXC ●D75N4H…C11N4H  VW3 AE 0801  11.000      EXC ●C13N4H, C16N4H  VW3 AE 0802  13.000      EXC ●C22N4H  VW3 AE 0827  22.000      EXC ●C25N4H, C31N4H  VW3 AE 0828  26.000      EXC ●C40N4H, C50N4H  VW3 AE 0829  30.000      EXC ●C63N4H  VW3 AE 0830  34.000   With  motor  choke  EXC ●D55N4H  VW3 AE 0807  9.000      EXC ●D75N4H…C11N4H  VW3 AE 0801  11.000      EXC ●C13N4H, C16N4H  VW3 AE 0802  13.000      EXC ●C22N4H  VW3 AE 0827  22.000      EXC ●C25N4H, C31N4H  VW3 AE 0828  26.000      EXC ●C40N4H, C50N4H  VW3 AE 0831  39.000       EXC ●C63N4H  VW3 AE 0832  43.000  Additional enclosure plinth   Without motor choke  EXC ●D55N4H  −  −  for cable entry via the top    EXC ●D75N4H…C31N4H  VW3 AE 0807  9.000      EXC ●C40N4H...C63N4H  VW3 AE 0808  18.000   With  motor  choke  EXC ●D55N4H  −  −      EXC ●D75N4H…C31N4H  VW3 AE 0807  9.000       EXC ●C40N4H…C63N4H  VW3 AE 0809  9.000     

Width of the cubicle    Altivar 61 Plus-LH    Options        72                      Width of the cubicle  The following tables specify the width of the enclosure that depends on the protection degree and the options used.  Protection degree IP23 / IP54  Side view    Basic device    Basic device incl. options  605 642 2002     a Altivar Plus     a a2 (1) a1 Altivar Plus                   ATV61  Option  a  a1  a2  EXC ●D55N4H  Without general options or with/without options depending on the power  400  −  400   With  general  options  600  −  600    Cable entry via the top  400  400  800  EXC ●D75N4H…EXC●C11N4H  With or without general options or options depending on the power  600  −  600    Cable entry via the top  600  400  1000  EXC ●C13N4H, EXC●C16N4H  With or without general options or options depending on the power  800  −  800    Cable entry via the top  800  400  1200  (1) Standard IP23 enclosure         

Width of the cubicle    Altivar 61 Plus-LH    Options                        73     Protection degree IP23 / IP54  Side view    Basic device    Basic device incl. options  605 642 2002     a Altivar Plus     a a1 a2 a3 (1) Altivar Plus                   ATV61  Option  a  a1  a2  a3  EXC ●C22N4H  With or without general options or options depending on the power  1200  −  −  1200    Cable entry via the top  1200  400  −  1600  EXC ●C25N4H, EXC●C31N4H  With or without general options or options depending on the power  1600  −  −  1600    Cable entry via the top  1600  400  −  2000  EXC ●C40N4H, EXC●C50N4H  With or without general options or options depending on the power (2)  2000  −  −  2000   Motor  choke  2000  −  400 2400    Cable entry via the top  2000  400  400  2800    Cable entry via the top + motor choke  2000  400  400  2800  EXC ●C63N4H  With or without general options or options depending on the power (2)  2400  −  −  2400   Motor  choke  2400  −  400 3200    Cable entry via the top  2400  400  400  2800    Cable entry via the top + motor choke  2400  400  400  3200  (1) Standard IP23 enclosure               

 

 

Schneider Electric Power Drives GmbH 10 / 2011 8 P02 540 EN.00/00 Due to evolution of standards and equipment, the characteristics indicated in texts and images ofthis document do not constitute a commitment on our part without confirmation.Design: Schneider Electric Power DrivesPhotos: Schneider Electric Power Drives Ruthnergasse 1A-1210 ViennaPhone:Fax: +43 (0) 1 29191 15 +43 (0) 1 29191 0